Property report

501 Osler Cir

Research this property with Analyst →

175,000 sqftSPINSbuilt 1986

Property at a glanceCommercial

Individual owner on record

2026 assessment
$69M OPA value, not a listing price
2027 published assessment
$69M Future roll, not the current tax bill
Neighborhood area
University City · West Powelton Approximate · based on ZIP 19104
From above · selected parcel outlined; choose a neighboring polygon to open it — imagery © Esri, Maxar
Open L&I record

3 violation rows marked OPEN in 1 active case

The actual City titles, code sections, case posture, and latest recorded inspections are shown here instead of only an aggregate count.

Open City history ↗
Case CF-2026-006837

Notice Of Violation

IN VIOLATION

Opened Jan 22, 2026 · Latest inspection FAILED · Jun 11, 2026

  • Inspection, Testing And MaintenanceF-907.8.5
  • Unapproved ConditionsF-604.6
  • Fdc Signage RequiredF-912.5

OPEN is the status in the fetched L&I file, not a new inspection by BlockReport. Read the notice for the cited condition and required correction, then verify the live case with L&I.

Assessment and City record timeline

The line tracks this property’s published City assessment. Markers show deeds, permits, inspections, licenses, violations, certifications, and appeals on their recorded dates. Select one to read the filing.

Assessments are tax-roll values, not sale prices or appraisals. OPA has published a 2027 assessment of $68,802,800. It is not yet the billed-year tax basis.

$0$50M$100M$69M200720112015201920232027
Property assessmentAssessmentL&I violationPermitInspectionLicenseCertification

Scroll horizontally to move through the years. Each icon sits on its recorded date; records without a day are labeled and centered within their year. Select one to explain the filing.

Highlight
Every dated record184 events · exact dates, newest first
  1. InspectionL&I investigation
  2. InspectionL&I investigation
  3. InspectionL&I investigation
  4. L&I violationINSPECTION, TESTING AND MAINTENANCE
  5. L&I violationSUPPRESSION SYSTEM TESTING & MAINTENANCE
  6. L&I violationUNAPPROVED CONDITIONS
  7. L&I violationFDC SIGNAGE REQUIRED
  8. L&I violationSTORAGE OF SAFETY DATA SHEETS
  9. L&I violationFIRE EXTINGUISHERS REQUIRED
  10. InspectionL&I investigation
  11. PermitAddition and/or Alteration
  12. PermitAddition and/or Alteration
  13. PermitAddition and/or Alterations
  14. CertificationEmergency and Standby Power Systems Certification
  15. PermitAlterations
  16. CertificationFire Alarm Certification
  17. PermitAddition and/or Alteration
  18. PermitAddition and/or Alteration
  19. PermitAddition and/or Alterations
  20. PermitAddition and/or Alterations
  21. PermitAddition and/or Alteration
  22. PermitAddition and/or Alteration
  23. PermitAlterations
  24. PermitAddition and/or Alterations
  25. PermitAddition and/or Alteration
  26. PermitAddition and/or Alterations
  27. PermitAddition and/or Alteration
  28. CertificationEmergency and Standby Power Systems Certification
  29. CertificationSprinkler Certification
  30. CertificationFire Alarm Certification
  31. InspectionL&I investigation
  32. InspectionL&I investigation
  33. CertificationFacade Report
  34. L&I violationFACADES
  35. InspectionL&I investigation
  36. InspectionL&I investigation
  37. L&I violationMANUAL FIRE ALARM BOX SIGNS
  38. L&I violationUNAPPROVED CONDITIONS
  39. L&I violationSUPPRESSION SYSTEM TESTING & MAINTENANCE
  40. L&I violationSUBMISSION OF CERTIFICATIONS
  41. CertificationEmergency and Standby Power Systems Certification
  42. CertificationSprinkler Certification
  43. CertificationFire Alarm Certification
  44. PermitAlterations
  45. PermitAddition and/or Alterations
  46. PermitAddition and/or Alteration
  47. PermitAddition and/or Alterations
  48. PermitAddition and/or Alteration
  49. PermitAddition and/or Alteration
  50. CertificationFire Alarm Certification
  51. PermitAddition and/or Alteration
  52. PermitAddition and/or Alteration
  53. InspectionL&I investigation
  54. PermitAddition and/or Alterations
  55. CertificationFire Alarm Certification
  56. PermitAddition and/or Alteration
  57. PermitAddition and/or Alterations
  58. PermitAlterations
  59. PermitRough-In
  60. PermitAddition and/or Alteration
  61. PermitAlterations
  62. PermitAddition and/or Alteration
  63. PermitAddition and/or Alterations
  64. PermitAddition and/or Alterations
  65. PermitAddition and/or Alterations
  66. PermitAddition and/or Alterations
  67. PermitAlterations
  68. PermitAddition and/or Alteration
  69. PermitAddition and/or Alteration
  70. InspectionL&I investigation
  71. L&I violationSECURING COMPRESSED CYLINDERS
  72. L&I violationFIRE SYSTEMS MAINTAINED
  73. L&I violationEXIT SIGN ILLUMINATION
  74. L&I violationEXTINGUISHER MOUNTED
  75. L&I violationTESTING/MAINTENANCE
  76. PermitNew Construction
  77. PermitNew Construction
  78. PermitNew Construction
  79. PermitAlterations
  80. PermitAddition and/or Alteration
  81. PermitNew Construction
  82. PermitNew Construction
  83. PermitElectrical
  84. PermitNew Construction
  85. PermitPlumbing
  86. PermitMechanical
  87. PermitAddition and/or Alteration
  88. PermitSuppression
  89. PermitMajor alteration
  90. PermitElectrical
  91. PermitAlterations
  92. PermitAddition and/or Alteration
  93. PermitNew Construction
  94. PermitMechanical
  95. PermitMajor alteration
  96. PermitSuppression
  97. PermitMechanical
  98. PermitSuppression
  99. PermitElectrical
  100. PermitPlumbing
  101. PermitMajor alteration
  102. PermitMajor alteration
  103. InspectionHCEU INSP (Housing Code Enforcement Unit inspection)
  104. L&I violationEGRESS-ASSEM OCC SIGNS
  105. L&I violationGENERATOR SET TEST REQ
  106. InspectionHCEU INSP (Housing Code Enforcement Unit inspection)
  107. PermitPlumbing
  108. PermitMechanical
  109. PermitElectrical
  110. PermitMajor alteration
  111. PermitElectrical
  112. InspectionHCEU INSP (Housing Code Enforcement Unit inspection)
  113. InspectionHCEU INSP (Housing Code Enforcement Unit inspection)
  114. L&I violationFIRE EXTING-NEEDS INSP/TAG (Fire extinguisher needs inspection and a current service tag)
  115. PermitMechanical
  116. PermitMechanical
  117. PermitMechanical
  118. PermitSuppression
  119. PermitSuppression
  120. PermitPlumbing
  121. PermitPlumbing
  122. PermitElectrical
  123. PermitElectrical
  124. PermitMechanical
  125. PermitElectrical
  126. PermitSuppression
  127. PermitMechanical
  128. PermitMajor alteration
  129. PermitMajor alteration
  130. PermitMajor alteration
  131. InspectionHCEU INSP (Housing Code Enforcement Unit inspection)
  132. PermitPlumbing
  133. PermitPlumbing
  134. PermitMajor alteration
  135. PermitElectrical
  136. PermitElectrical
  137. L&I violationHAZMAT-ID SIGNS REQ¿D
  138. InspectionHCEU INSP (Housing Code Enforcement Unit inspection)
  139. PermitMajor alteration
  140. PermitMechanical
  141. CertificationFacade Report
  142. PermitElectrical
  143. PermitPlumbing
  144. PermitMajor alteration
  145. PermitSuppression
  146. PermitAlteration
  147. PermitSuppression
  148. PermitElectrical
  149. PermitMajor alteration
  150. PermitMechanical
  151. PermitMechanical
  152. PermitPlumbing
  153. PermitSuppression
  154. PermitMajor alteration
  155. LicenseUNIVERSITY OF PENNA TRUSTEES: High Rise L&I license filing initially issued
  156. PermitElectrical
  157. PermitPlumbing
  158. PermitMajor alteration
  159. PermitMechanical
  160. PermitElectrical
  161. PermitSuppression
  162. LicenseUNIVERSITY OF PENNA TRUSTEES: Dumpster License - Private Property L&I license filing initially issued
  163. PermitMechanical
  164. PermitPlumbing
  165. PermitMajor alteration
  166. PermitElectrical
  167. PermitMajor alteration
  168. PermitMechanical
  169. PermitNew Construction
  170. PermitElectrical
  171. PermitSuppression
  172. PermitMajor alteration
  173. PermitFast form building
  174. PermitMechanical
  175. PermitPlumbing
  176. PermitMajor alteration
  177. PermitFast form building
  178. PermitElectrical
  179. PermitMechanical
  180. PermitPlumbing
  181. PermitMajor alteration
  182. PermitMechanical
  183. PermitMajor alteration
  184. PermitFast form building

Verify the public record

$0/year estimated property tax

2026 taxable assessment $0 × 1.3998%. This is an estimate, not a bill or account balance. The City maintains payments, credits, interest, and the current amount due.

OPA has published a 2027 assessment of $68,802,800. It is not the 2026 billed-year value.

Current City balanceCheck Tax Center

Payments, credits, interest, and the current amount due are maintained by the City.

OPA 773003010
Open Philadelphia Tax Center →Use “View period balance” to inspect each tax year.
Exemption classificationFull assessment exemption shown

2026 OPA shows a zero or de minimis taxable assessment. The open assessment split does not establish the exemption's legal basis, continuing eligibility, or treatment after a transfer.

Historical delinquency sources No current conclusion

This parcel did not match the June 2022 delinquency snapshot. That absence does not confirm the account is current today.

For a purchase, refinance, or closing, request the City’s official Property Payoff statement in Tax Center under “More options.”

Property report

Commercial property

Commercial, recorded in the City's commercial category. The public record and owner trail follow.

6 open violations

What it is
Commercial Misc Research Masonry+Oth
Owner
Individual owner on record Individual name redacted
$ / sq ft
$393 above the $151 median for 7,668 commercial parcels citywide
Interior area
175,000 sqft
Lot size
39,000 sqft
Built
1986
Zoning
SPINS

Block context

500 block of Osler Cir. Compare parcels, ownership, and public-record history.

See the whole block →

Next door: 515 Osler Cir  ·  500 Osler Cir

No business or residential license records

No business license or residential registration matched this OPA parcel in the latest City data.

Verify with the City ↗
Open every source row 184 dated rows
  1. InvestigationL&I investigation

    Case CF-2026-006837 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  2. InvestigationL&I investigation

    Case CF-2026-006837 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  3. InvestigationL&I investigation

    Case CF-2026-006837 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  4. ViolationINSPECTION, TESTING AND MAINTENANCE

    Case CF-2026-006837 · Violation VI-2026-004425 · Code F-907.8.5 · OPEN

    The individual violation row was marked open in the assembled City file; verify the live notice and any later inspection.

  5. ViolationSUPPRESSION SYSTEM TESTING & MAINTENANCE

    Case CF-2026-006837 · Violation VI-2026-004426 · Code F-903.5 · COMPLIED

    Resolution: COMPLIED - LICENSE/CERTIFICATE/REPORT OBTAINED City marked this violation complied with; check the resolution date and live case for what was accepted.

  6. ViolationUNAPPROVED CONDITIONS

    Case CF-2026-006837 · Violation VI-2026-004427 · Code F-604.6 · OPEN

    The individual violation row was marked open in the assembled City file; verify the live notice and any later inspection.

  7. ViolationFDC SIGNAGE REQUIRED

    Case CF-2026-006837 · Violation VI-2026-004428 · Code F-912.5 · OPEN

    The individual violation row was marked open in the assembled City file; verify the live notice and any later inspection.

  8. ViolationSTORAGE OF SAFETY DATA SHEETS

    Case CF-2026-006837 · Violation VI-2026-004429 · Code F-5003.4.1 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  9. ViolationFIRE EXTINGUISHERS REQUIRED

    Case CF-2026-006837 · Violation VI-2026-004430 · Code F-906.1 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  10. InvestigationL&I investigation

    Case CF-2023-124184 · PASSED

    The cited inspection visit was marked passed.

  11. PermitAddition and/or Alteration

    Permit EP-2025-011936 · Completed

    Provide and install sixteen (16) 1x4 recessed light fixtures, nine (9) linear feet of under-cabinet lighting, four (4) downlights, four (4) exit signs, and seven (7) ceiling-mounted sensors. Install two (2) switches, eighteen (18) duplex receptacle outlets, and five (5) quad receptacle outlets. Provide backboxes and conduit pathways to the ceiling for six (6) tele/data locations and four (4) duress buttons. Install one (1) security camera and one (1) card reader. Modify the existing fire alarm system to include one (1) speaker/strobe device. All work to be done according to the 2017 NEC, 2016 NFPA 72 and per approved plans.

  12. PermitAddition and/or Alteration

    Permit EP-2025-010331 · Issued

    F&I new emergency feeder from level 1 to penthouse, F&I new ATS, panels, breakers, and VFDs. Disconnect old mechanical equipment and connect to new. Replace existing lightning in kind, modify existing fire alarm . ALL WORK IS TO BE DONE ACCORDING TO APPROVED DRAWINGS-2017 NEC,2016 NFPA-72.

  13. PermitAddition and/or Alterations

    Permit FP-2025-002284 · Completed

    EZ PERMIT SPRINKLER RELOCATION (NFPA 13)- For the relocation of sprinkler heads as per attached standards. Deviations from these standards require submission of construction and site plans. Relocate 4 Heads

  14. CertificationEmergency and Standby Power Systems Certification

    Certification BC-2025-030897 · Certified

    Expires 2026-11-12

  15. PermitAlterations

    Permit PP-2025-014528 · Completed

    To install 9 fixtures, including piping from the mains, for 1 sink, 4 lavs, 2 toilets & 2 showers. Installed to the 2018 Philadelphia Plumbing Code section 919(Philadelphia Single Stack/venting System **************************ALL PIPING MUST BE METALLIC**********************************************

  16. CertificationFire Alarm Certification

    Certification BC-2025-030297 · Certified

    Expires 2026-10-23

  17. PermitAddition and/or Alteration

    Permit CP-2025-003762 · Completed

    FOR LEVEL II ALTERATIONS TO AN EXISTING COMMERCIAL BUILDING FOR USE AS AN APARTMENT BUILDING (B OCCUPANCY), ALTERATIONS TO INCLUDE THE ERECTION OF PARTITION WALLS, PROVIDE FINISHES/FURNISHINGS AND ACCESSIBILITY IMPROVEMENTS THROUGHOUT. ALL WORK TO BE DONE PER APPROVED PLANS. IF FIELD CONDITIONS VARY CONTACT DESIGN ENGINEER PRIOR TO THE START OF ANY WORK. SEPARATE PERMITS TO BE OBTAINED FOR ALL OTHER WORK.

  18. PermitAddition and/or Alteration

    Permit EP-2025-008716 · Completed

    Install one (1) light fixture, eight (8) receptacles, power for (1) EF

  19. PermitAddition and/or Alterations

    Permit MP-2025-004538 · Completed

    FOR THE INSTALLATION OF REGISTERS, DIFFUSERS, AND APPLIANCES WITH ASSOCIATED DUCTWORK. APPLIANCES TO BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS. ALL WORK TO BE DONE PER APPROVED PLANS. IF FIELD CONDITIONS VARY CONTACT DESIGN ENGINEER PRIOR TO THE START OF ANY WORK. SEPARATE PERMITS REQUIRED FOR ALL OTHER WORK.

  20. PermitAddition and/or Alterations

    Permit FP-2025-001646 · Completed

    Relocate (1) sprinkler in lab 310B

  21. PermitAddition and/or Alteration

    Permit CP-2025-003204 · Completed

    FOR A LEVEL I INTERIOR ALTERATIONS TO AN EXISTING LABORATORY SPACE (LAB #310B). BUILDING IS BE FULLY SPRINKLERED. ALL WORK TO BE DONE PER APPROVED PLANS. IF FIELD CONDITIONS VARY CONTACT DESIGN ENGINEER PRIOR TO THE START OF ANY WORK. SEPARATE PERMITS TO BE OBTAINED FOR ALL OTHER WORK. **SEPARATE PERMITS REQUIRED FOR ELECTRICAL, MECHANICAL, PLUMBING & FIRE SUPPRESSION WORK**

  22. PermitAddition and/or Alteration

    Permit CP-2025-003646 · Issued

    FOR INSTALLATION OF EQUIPMENT PLATFORM ON THE ROOF TOP AS PER APPROVED PLANS.

  23. PermitAlterations

    Permit PP-2025-008856 · Completed

    INSTALL LAB SINK ACCORDING TO THE 2018 PPC AND PER PLANS.

  24. PermitAddition and/or Alterations

    Permit MP-2025-003671 · Completed

    FOR THE INSTALLATION OF REGISTERS, DIFFUSERS, AND APPLIANCES WITH ASSOCIATED DUCTWORK. APPLIANCES TO BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER’S SPECIFICATIONS. FOR USE AS PREVIOUSLY APPROVED. ALL WORK TO BE DONE PER APPROVED PLANS. IF FIELD CONDITIONS VARY CONTACT DESIGN ENGINEER PRIOR TO THE START OF ANY WORK. SEPARATE PERMITS TO BE OBTAINED FOR ALL OTHER WORK. 12/6/25 AMENDMENT: REMOVAL OF F/S DAMPER AND USE OF FIRE BLANKET FOR SHAFT PENETRATION OF NEW EXHAUST DUCT IN ORDER TO ADVOID ANY NEGATIVE IMPACTS ON ONGOING EXPERIMENTS.

  25. PermitAddition and/or Alteration

    Permit EP-2025-006599 · Completed

    Install duplex receptacles qty. 16, Install GFI receptacles qty. 2, Install power for FCU qty. 2. Install power for FFU qty. 3. Install low voltage switch qty. 1. Install occupancy sensor qty. 1. Install room controller, Install type A1 qty. 4. Installation shall comply with 2017 NEC. SECO job number 6145.

  26. PermitAddition and/or Alterations

    Permit FP-2025-001456 · Completed

    EZ PERMIT SPRINKLER RELOCATION (NFPA 13)- For the relocation of sprinkler heads as per attached standards. Deviations from these standards require submission of construction and site plans. Relocate 4 Heads

  27. PermitAddition and/or Alteration

    Permit CP-2025-002976 · Completed

    FOR A LEVEL I INTERIOR ALTERATIONS TO AN EXISTING LABORATORY SPACE (LAB #625) . BUILDING IS BE FULLY SPRINKLERED.N** ALL WORK TO BE DONE PER APPROVED PLANS.** IF FIELD CONDITIONS VARY CONTACT DESIGN PROFESSIONAL PRIOR TO THE START OF ANY WORK. ** SEPARATE PERMITS TO BE OBTAINED FOR ALL OTHER WORK.**

  28. CertificationEmergency and Standby Power Systems Certification

    Certification BC-2024-031853 · Certified

    Expires 2025-11-13

  29. CertificationSprinkler Certification

    Certification BC-2024-032207 · Certified

    Expires 2025-10-23

  30. CertificationFire Alarm Certification

    Certification BC-2024-030624 · Certified

    Expires 2025-10-23

  31. InvestigationL&I investigation

    Case CF-2023-124708 · PASSED

    The cited inspection visit was marked passed.

  32. InvestigationL&I investigation

    Case CF-2023-124708 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  33. CertificationFacade Report

    Certification BC-2024-018909 · Safe

    Expires 2029-02-15

  34. ViolationFACADES

    Case CF-2023-124708 · Violation VI-2023-094789 · Code PM15-315.2 · COMPLIED

    Resolution: COMPLIED - LICENSE/CERTIFICATE/REPORT OBTAINED City marked this violation complied with; check the resolution date and live case for what was accepted.

  35. InvestigationL&I investigation

    Case CF-2023-124708 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  36. InvestigationL&I investigation

    Case CF-2023-124184 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  37. ViolationMANUAL FIRE ALARM BOX SIGNS

    Case CF-2023-124184 · Violation VI-2023-094354 · Code F-907.4.2.4 · CLOSED

    Resolution: CLOSED - REISSUED/REWRITTEN City marked the record closed; open the case for the closing reason.

  38. ViolationUNAPPROVED CONDITIONS

    Case CF-2023-124184 · Violation VI-2023-094352 · Code F-604.6 · CLOSED

    Resolution: CLOSED - REISSUED/REWRITTEN City marked the record closed; open the case for the closing reason.

  39. ViolationSUPPRESSION SYSTEM TESTING & MAINTENANCE

    Case CF-2023-124184 · Violation VI-2023-094347 · Code F-903.5 · CLOSED

    Resolution: CLOSED - REISSUED/REWRITTEN City marked the record closed; open the case for the closing reason.

  40. ViolationSUBMISSION OF CERTIFICATIONS

    Case CF-2023-124184 · Violation VI-2023-094348 · Code F-901.6.4.2 · CLOSED

    Resolution: CLOSED - REISSUED/REWRITTEN City marked the record closed; open the case for the closing reason.

  41. CertificationEmergency and Standby Power Systems Certification

    Certification BC-2024-011750 · Certified

    Expires 2024-11-29

  42. CertificationSprinkler Certification

    Certification BC-2024-004178 · Certified

    Expires 2024-10-24

  43. CertificationFire Alarm Certification

    Certification BC-2023-022432 · Certified

    Expires 2024-10-24

  44. PermitAlterations

    Permit PP-2023-007224 · Completed

    F&I (1) Faucet for Lab Sink, (2) C02 Manifolds, (5) Vacuum Turrets, (6) C02 Turrets, (2) Cylinder Racks and all domestic, sanitary, medical piping

  45. PermitAddition and/or Alterations

    Permit FP-2023-001507 · Completed

    EZ PERMIT SPRINKLER RELOCATION (NFPA 13)- For the Relocation of Sprinkler Heads as per attached standards. Deviations from these standards require submission of construction and site plans. Modify (2) sprinkler heads to accommodate interior alterations in 7th floor tenant space Clinical Research Building, 7th floor

  46. PermitAddition and/or Alteration

    Permit EP-2023-006142 · Completed

    Remove & install new surface mount 3000 Series Wiremold & devices as shown on plan E101. New device branch circuits from existing panels as indicated on plan E101. New lighting & control devices as shown on E102 as per 2017 nec

  47. PermitAddition and/or Alterations

    Permit MP-2023-002374 · Completed

    FOR THE INSTALLATION OF REGISTERS, DIFFUSERS, AND APPLIANCES WITH ASSOCIATED DUCTWORK. APPLIANCES TO BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS. ALL WORK TO BE DONE PER APPROVED PLANS. IF FIELD CONDITIONS VARY CONTACT DESIGN ENGINEER PRIOR TO THE START OF ANY WORK. SEPARATE PERMITS REQUIRED FOR ALL OTHER WORK.

  48. PermitAddition and/or Alteration

    Permit CP-2023-003510 · Completed

    FOR A LEVEL II INTERIOR ALTERATIONS TO A TENANT SPACE ON THE 7TH FLOOR LEVEL OF AN EXISTING STRUCTURE. ALTERATIONS TO INCLUDE THE ERECTION OF PARTITION WALLS, PROVIDE FINISHES/FURNISHINGS, THROUGHOUT. BUILDING IS FULLY SPRINKLERED. ALL WORK TO BE DONE PER APPROVED PLANS. IF FIELD CONDITIONS VARY CONTACT DESIGN PROFESSIONAL PRIOR TO THE START OF ANY WORK. SEPARATE PERMITS TO BE OBTAINED FOR ALL OTHER WORK.

  49. PermitAddition and/or Alteration

    Permit CP-2023-001674 · Cancelled

    FOR LEVEL II ALTERATIONS PER APPROVED PLANS. SEPARATE PERMITS REQUIRED FOR MECHANICAL, ELECTRICAL AND PLUMBING.

  50. CertificationFire Alarm Certification

    Certification BC-2022-018173 · Certified

    Expires 2023-10-20

  51. PermitAddition and/or Alteration

    Permit EP-2022-005827 · Completed

    Install lighting fixtures, lighting control devices, power devices to include wiring and terminations as per NEC 2017. Provide electrical demolition and temporary lighting as necessary.

  52. PermitAddition and/or Alteration

    Permit CP-2021-008947 · Expired

    LEVEL II ALTERATIONS (NO CHANGE OF OCCUPANCY) FOR DEMOLITION OF CONNECTING BRIDGE (SEE ALSO PERMIT CP-2021-008822) AND INFILL OF EXTERIOR WALL OPENING AS PER APPROVED PLANS. *2018 IEBC REVIEW*

  53. InvestigationL&I investigation

    Case CF-2020-057493 · PASSED

    The cited inspection visit was marked passed.

  54. PermitAddition and/or Alterations

    Permit FP-2021-002788 · Completed

    EZ PERMIT SPRINKLER RELOCATION (NFPA 13)- For the Relocation of Sprinkler Heads as per attached standards. Deviations from these standards require submission of construction and site plans. Relocate (1) Sprinkler Head in the Clinical Research Building, S-4 (CP-2021-001691)

  55. CertificationFire Alarm Certification

    Certification BC-2021-005493 · Certified

    Expires 2022-10-12

  56. PermitAddition and/or Alteration

    Permit EP-2021-005174 · Completed

    Relocate (5) wall switches and (1) occupancy sensor. Provide (10) new 1x4 light fixtures, (2) ceiling sensors, (2) switches, and (2) room controllers. Provide approximately 20' of surface mounted raceway with (9) duplex outlets. Provide (9) additional duplex outlets, (2) duplex outlets in existing surface mounted raceway, (14) backboxes with pathway stubbed to accessible ceilings, and power to one fan coil unit as per 2017 NEC.

  57. PermitAddition and/or Alterations

    Permit MP-2021-003206 · Completed

    For alterations to the ductwork and piping layout within 5th floor Group B laboratories on the 5th floor of an existing eight (8) story attached structure, as per plans; see CP-2021-001691 for associated building permit; no other work on this permit. APPLIANCES TO BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS. ALL WORK TO BE DONE PER APPROVED PLANS. IF FIELD CONDITIONS VARY CONTACT DESIGN ENGINEER PRIOR TO THE START OF ANY WORK. SEPARATE PERMITS TO BE OBTAINED FOR ALL OTHER WORK.

  58. PermitAlterations

    Permit PP-2021-010138 · Expired

    Demo length of pipe and cap. No new fixtures or installation

  59. PermitRough-In

    Permit EP-2021-005177 · Completed

    Rough-In Permit for EP-2021-005174 Relocate (5) wall switches and (1) occupancy sensor. Provide (10) new 1x4 light fixtures, (2) ceiling sensors, (2) switches, and (2) room controllers. Provide approximately 20' of surface mounted raceway with (9) duplex outlets. Provide (9) additional duplex outlets, (2) duplex outlets in existing surface mounted raceway, (14) backboxes with pathway stubbed to accessible ceilings, and power to one fan coil unit. AS PER NEC 2017

  60. PermitAddition and/or Alteration

    Permit CP-2021-001691 · Completed

    LEVEL II INTERIOR ALTERATIONS (NO CHANGE OF OCCUPANCY) FOR RENOVATIONS TO FIFTH FLOOR LAB SPACE WITHIN AN EXISTING EDUCATIONAL FACILITY (CLINICAL RESEARCH BUILDING, S-4) AS PER APPROVED PLANS. EXISTING BUILDING FULLY SPRINKLERED. *2018 IEBC REVIEW* **SEPARATE PERMITS REQUIRED FOR ANY MEP OR FIRE SUPPRESSION WORK**

  61. PermitAlterations

    Permit PP-2021-003646 · Completed

    To install 4 lab sinks. Also install 3 eye washes (Other on list of fixtures). 2 of the sinks will have new sanitary & water piping from the mains. 2 of the sinks will be installed to existing plumbing pipes.

  62. PermitAddition and/or Alteration

    Permit EP-2021-002184 · Completed

    Replace lighting, wiring devices, lighting controls, branch circuit wiring, lab table devices as per 2017 nec

  63. PermitAddition and/or Alterations

    Permit MP-2021-001439 · Expired

    EZ PERMIT DUCTWORK & WARM-AIR APPLIANCES- For the installation of New Ductwork, Registers/Grilles/Diffusers, and Warm-Air Appliances as per attached standards. Deviations from these standards require submission of construction and site plans. EACH HVAC UNIT TO BE SELF-CONTAINED WITHIN EACH DWELLING UNIT. NO PENETRATIONS OF RATED ASSEMBLIES. Furnish and Install supply diffuser with flexible ductwork in 410C. Furnish and install return grill in 410E. Replace t-stats, and balance.

  64. PermitAddition and/or Alterations

    Permit FP-2020-002447 · Completed

    Relocate 2 sprinkler heads Rooms 278-278A Only

  65. PermitAddition and/or Alterations

    Permit MP-2020-004288 · Completed

    For alterations to the ductwork and piping layout within rooms 505, 505A, 514, 515, and 515A used as Group B laboratories on the 5th floor of an existing eight (8) story attached structure, as per plans; see CP-2020-003738 for associated building permit; no other work on this permit.

  66. PermitAddition and/or Alterations

    Permit FP-2020-001694 · Completed

    Relocate Sprinkler Heads; Demo and relocate sprinkler line around room. 2 concealed heads, 1 SSU Head

  67. PermitAlterations

    Permit PP-2020-008337 · Completed

    For minor construction work at the subject property in accordance with all applicable provisions of the Philadelphia Code, all references codes and standards, and the attached EZ Standard, where included. Deviation from this standard shall result in permit revocation. A separate permit from the Philadelphia Department of Streets is required for any sidewalk and street closures. All means of pedestrian protection required at the site in accordance with the Philadelphia Building Code Chapter 33 shall be in place prior to start of work.

  68. PermitAddition and/or Alteration

    Permit EP-2020-007013 · Completed

    Relocate (4) light fixtures, provide 30' of surface mounted raceway, provide (21) duplex outlets, (4) gfi outlets, (15) quad outlets, provide wiring for outlets per 2017 nec.

  69. PermitAddition and/or Alteration

    Permit CP-2020-003738 · Completed

    For Level I Alterations (without a change in occupancy) throughout rooms 505, 505A, 514, 515, and 515A as part of a Group B occupancy (laboratories) on the 5th floor of an existing eight (8) story attached structure, as per plans; separate permits required for all MEP/FSP work; sprinklers installed throughout as per NFPA 13; existing means of egress to be available to occupants at all times during work.

  70. InvestigationL&I investigation

    Case CF-2020-057493 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  71. ViolationSECURING COMPRESSED CYLINDERS

    Case CF-2020-057493 · Violation VI-2020-032168 · Code FC-13-3003.5.3 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  72. ViolationFIRE SYSTEMS MAINTAINED

    Case CF-2020-057493 · Violation VI-2020-032169 · Code FC-13-901.6 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  73. ViolationEXIT SIGN ILLUMINATION

    Case CF-2020-057493 · Violation VI-2020-032170 · Code FC-13-1007.2 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  74. ViolationEXTINGUISHER MOUNTED

    Case CF-2020-057493 · Violation VI-2020-032171 · Code FC-13-906.7 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  75. ViolationTESTING/MAINTENANCE

    Case CF-2020-057493 · Violation VI-2020-032172 · Code FC-13-904.11.2 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  76. PermitNew Construction

    Permit 1044105 · Expired

    FOR ALTERATIONS TO THE EXISTING MECHANICAL SYSTEM WITHIN LABORATORY ROOM 274B ON THE 2ND FLR OF AN EXISTING MEDICAL RESEARCH BUILDING, AS PER PLANS; NO OTHER WORK ON THIS PERMIT.

  77. PermitNew Construction

    Permit 1022336 · Completed

    DEMO EXISTING LIGHTING AND POWER. INSTALL 4 LIGHTS/16 RECEPTACLES/3 SWITCHES. RELOCATE 2 HORN STROBES AS PER 2017 NEC AND NFPA 72 (WEST DIST) RELOCATE 2 EXISTING HORN STROBES. AS PER THE 2016 NFPA72.

  78. PermitNew Construction

    Permit 1020943 · Completed

    FOR THE INSTALLATION OF REGISTERS, DIFFUSERS AND APPLIANCES WITH ASSOCIATED DUCTWORK. APPLIANCES TO BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS. ALL WORK TO BE DONE PER APPROVED PLANS. IF FIELD CONDITIONS VARY CONTACT DESIGN ENGINEER PRIOR TO THE START OF ANY WORK. SEPARATE PERMITS TO BE OBTAINED FOR ALL OTHER WORK.

  79. PermitAlterations

    Permit 1020997 · Completed

    REMOVE & REPLACE 2-SINKS & RE ROUGH 1-NEW SINK THE INSTALLATION WILL COMPLY WITH THE PHILADELPHIA PLUMBING CODE 2004

  80. PermitAddition and/or Alteration

    Permit 1016384 · Completed

    NO CHANGE IN USE AND OCCUPANCY CLASSIFICATION. INTERIOR ALTERATIONS (PRESCRIPTIVE METHOD) TO THE 2ND FLOOR LEVEL IN AN EXISTING CLINICAL RESEARCH BUILDING (S-4) AS PER APPROVED PLANS. SEPARATE PERMIT REQUIRED FOR ANY MEP AND FIRE SUPPRESSION WORK.

  81. PermitNew Construction

    Permit 1004017 · Completed

    INSTALL 60 RECEPTACLES USE EXISTING CIRCUITS MADE AVAILABLE FROM DEMO. INSTALL 40 LIGHTS 10 SWITCHED AND MOTION SENSORS AS PER 2017 NEC (WEST DIST) **THERE IS NO FIRE ALARM ON THIS PERMIT**

  82. PermitNew Construction

    Permit 1004040 · Completed

    FOR ALTERATIONS TO AN EXISTING MECHANICAL/HVAC SYSTEM ON THE PARTIAL 4TH AND 5TH FLRS OF AN EXISTING GROUP B LABORATORY BUILDING, AS PER PLANS; NO OTHER WORK ON THIS PERMIT; SEE AP#991655 FOR ALTERATION PERMIT.

  83. PermitElectrical

    Permit 1001127 · COMPLETED

    REMOVE EXISTING ELECTRICAL DEVICES AND FIXTURES. FURNISH AND INSTALL 24 NEW LIGHT FIXTURES. FURNISH AND INSTALL 72 RECEPTACLES. PROVIDE CONDUIT AND WIRING. CONNECT TO EXISTING ELECTRICAL PANELS AS PER 2017 NEC (WEST DIST)

  84. PermitNew Construction

    Permit 1005012 · Completed

    EZ PERMIT SPRINKLER RELOCATION (NFPA 13)- For the relocation of sprinkler heads as per attached standard. Deviations from this standard will result in permit revocation and require submission of construction plans.

  85. PermitPlumbing

    Permit 1002809 · COMPLETED

    INSTALL WASTE WANT WATER LINES, NEW SANITARY VENT ND DOMESTIC WATER TO 1 NEW SINK AS PER 2004 PPC

  86. PermitMechanical

    Permit 1002439 · COMPLETED

    FOR THE INSTALLATION OF MECHANICAL WORK TO INCLUDE REGISTERS/DIFFUSER, SUPPLY/EXHAUST DUCTWORK, AND ALL OTHER WORK AS PER APPROVED PLANS. SEPARATE PERMIT REQUIRED FOR ANY ELECTRICAL AND PLUMBING WORK.

  87. PermitAddition and/or Alteration

    Permit 991655 · Completed

    LEVEL II INTERIOR ALTERATIONS (NO CHANGE OF OCCUPANCY) FOR RENOVATIONS TO FOURTH AND FIFTH FLOOR LABS IN EXISTING CLINICAL RESEARCH BUILDING (S-4) AS PER APPROVED PLANS. ALTERATIONS TO INCLUDE THE ERECTION OF PARTITION WALLS, PROVIDE FINISHES AND ACCESSIBILITY IMPROVEMENTS THROUGHOUT. ALL WORK TO BE DONE PER APPROVED PLANS. EXISTING BUILDING FULLY SPRINKLERED. *2018* **SEPARATE PERMITS REQUIRED FOR ANY MEP OR FIRE SUPPRESSION WORK**

  88. PermitSuppression

    Permit 993078 · COMPLETED

    EZ PERMIT SPRINKLER RELOCATION (NFPA 13)-RELOCATE EIGHT(8) SPRINKLER HEADS ON THE FORTH(4TH) FLOOR FOR THE RELOCATION OF SPRINKLER HEADS AS PER ATTACHED STANDARDS. DEVIATIONS FROM THESE STANDARDS REQUIRE SUBMISSION OF CONSTRUCTION AND SITE PLANS.

  89. PermitMajor alteration

    Permit 985072 · COMPLETED

    LEVEL II INTERIOR ALTERATIONS (NO CHANGE OF OCCUPANCY) FOR RENOVATIONS TO FOURTH FLOOR LABS IN EXISTING CLINICAL RESEARCH BUILDING (S-4) AS PER APPROVED PLANS. EXISTING BUILDING FULLY SPRINKLERED. *2018* **SEPARATE PERMITS REQUIRED FOR ANY MEP OR FIRE SUPPRESSION WORK**

  90. PermitElectrical

    Permit 866305 · COMPLETED

    REPLACE 2- LIGHTS, 4- RECEPTACLES WITH 4- GFCI RECEPTACLES, INSTALL 1- 20A CIRCUIT TO EXISTING 20- BREAKER IN EXISTING PANEL. REPLACE EXISTING SWITCH WITH TIMER SWITCH.... IN ACCORDANCE WITH 2008 NEC (RESEARCH LAB)

  91. PermitAlterations

    Permit 864804 · Expired

    CONNECT TO EXISTING SANITARY AND WATER PIPING TO FFED 2 SINKS (UNIVERSITY COMPLEX)

  92. PermitAddition and/or Alteration

    Permit 861543 · Expired

    NO CHANGE IN USE AND OCCUPANCY CLASSIFICATION. INTERIOR ALTERATIONS AS PER APPROVED PLANS. SEPARATE PERMIT REQUIRED FOR ANY MEP WORK.

  93. PermitNew Construction

    Permit 794837 · Issued

    DEMO AND REMOVE EXISTING LIGHTS AND RECEPTS,FURNISH AND INSTALL 14-LIGHT FIXTURES,22-RECEPTS,CONNECT TO EXISTING CIRCUITS IN EXISTING ELECTRICAL PANELS WITH NO FIRE ALARM WORK AS PER 2008 NEC (NORTH DISTRICT)

  94. PermitMechanical

    Permit 788443 · COMPLETED

    FOR THE DEMOLITION OF EXSITING DUCTWORK AND THE INSTALLATION OF FOUR (4) VAV BOXES WITH ASSOCIATED DUCTWORK/REGISTERS/DIFFUERS, AS PER APPROVED PLANS.

  95. PermitMajor alteration

    Permit 775474 · COMPLETED

    LEVEL II INTERIOR ALTERATIONS (NO CHANGE OF OCCUPANCY) FOR RENOVATIONS TO FIRST FLOOR LABS IN EXISTING CLINICAL RESEARCH BUILDING (S-4) AS PER APPROVED PLANS. EXISTING BUILDING FULLY SPRINKLERED. **SEPARATE PERMITS REQUIRED FOR ANY MEP OR FIRE SUPPRESSION WORK**

  96. PermitSuppression

    Permit 780360 · COMPLETED

    EZ PERMIT SPRINKLER RELOCATION (NFPA 13)- FOR THE RELOCATION OF SPRINKLER HEADS AS PER ATTACHED STANDARD. DEVIATIONS FROM THIS STANDARD WILL RESULT IN PERMIT REVOCATION AND REQUIRE SUBMISSION OF CONSTRUCTION PLANS.

  97. PermitMechanical

    Permit 768890 · COMPLETED

    FOR THE INSTALLATION OF DUCTWORK, REGISTERS/DIFFUSERS, AND ALL OTHER WORK AS PER APPROVED PLANS. SEPARATE PERMIT REQUIRED FOR ANY ELECTRICAL AND PLUMBING WORK.

  98. PermitSuppression

    Permit 774798 · COMPLETED

    RELOCATE 1 SPRINKLER ON THE 2ND FLOOR

  99. PermitElectrical

    Permit 765174 · COMPLETED

    CONNECT TO EXISTING CIRCUITS, PAELS, REMOVE/RESEARCH/REPLACE EXISTING LLIGHTING FIXTRUES & DEVICES, PROVIDE NEW DEVICE/FIXTURES AS PER 2008 NEC (WEST DISTRICT) RELOCATE/PROVED NEW FIRE ALARM DEVICES TIED INTO BOX AND STUBS AS PER NFPA72

  100. PermitPlumbing

    Permit 768885 · COMPLETED

    DEMO 3 SINKS AND INSTALL 1 INDIRECT SAFE WASTE (UNIVERSITY COMPLEX)THE INSTALLATION SHALL COMPLY WITH THE PHILADELPHIA PLUMBING CODE, 2004

  101. PermitMajor alteration

    Permit 764295 · COMPLETED

    NO CHANGE IN USE AND OCCUPANCY CLASSIFICATION. INTERIOR ALTERATIONS AS PER APPROVED PLANS. SEPARATE PERMIT REQUIRED FOR ANY MEP AND FIRE SUPPRESSION WORK.

  102. PermitMajor alteration

    Permit 669663 · COMPLETED

    MINOR FACADE REPAIR AND INCLUDES COVERED WALKWAYS INSTALLATION AS PER PLANS.** STREETS DEPARTMENT PERMIT REQUIRED FOR PLATFORMS PROJECTING OVER THE SIDEWALK PRIOR TO THE START OF WORK.**

  103. InvestigationHCEU INSP (Housing Code Enforcement Unit inspection)

    Case 510801 · PASSED

    A legacy L&I inspection label. The unit inspected housing for property-maintenance, fire-prevention, and related code compliance; the separate status says how that visit ended. The cited inspection visit was marked passed.

  104. ViolationEGRESS-ASSEM OCC SIGNS

    Case 510801 · Violation 3773601 · Code FC-1004.3/1 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  105. ViolationGENERATOR SET TEST REQ

    Case 510801 · Violation 3773602 · Code FC-604.4/2 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  106. InvestigationHCEU INSP (Housing Code Enforcement Unit inspection)

    Case 510801 · FAILED

    A legacy L&I inspection label. The unit inspected housing for property-maintenance, fire-prevention, and related code compliance; the separate status says how that visit ended. The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  107. PermitPlumbing

    Permit 611923 · COMPLETED

    CONNECT TO EXISTING SERVICES TO INSTALL 1- NEW SINK

  108. PermitMechanical

    Permit 612360 · COMPLETED

    EZ PERMIT DUCTWORK & WARM-AIR APPLIANCES- FOR THE INSTALLATION OF NEW DUCTWORK, REGISTERS/GRILLES/DIFFUSERS, AND WARM-AIR APPLIANCES AS PER ATTACHED STANDARD. DEVIATIONS FROM THIS STANDARD WILL RESULT IN PERMIT REVOCATION AND REQUIRE SUBMISSION OF CONSTRUCTION PLANS. INSTALL 1 NEW EXHAUST REGISTER

  109. PermitElectrical

    Permit 611460 · COMPLETED

    REMOVE AND RELOCATE LIGHT FIXTURES DEMO WIRE MOLD AND INSTALL POWER AND LIGHTING

  110. PermitMajor alteration

    Permit 597526 · COMPLETED

    LEVEL II ALTERATIONS AS PER PLAN.

  111. PermitElectrical

    Permit 574111 · COMPLETED

    ASSIST WITH THE INSTALLATION OF BOOTH & EQUIPMENT ASSEMBLE IN HEARING BOOTH POWER TO THE BOOTH FINAL CONNECTION ONLY (MEDICAL FACILITY) AS PER NEC 2008

  112. InvestigationHCEU INSP (Housing Code Enforcement Unit inspection)

    Case 453264 · PASSED

    A legacy L&I inspection label. The unit inspected housing for property-maintenance, fire-prevention, and related code compliance; the separate status says how that visit ended. The cited inspection visit was marked passed.

  113. InvestigationHCEU INSP (Housing Code Enforcement Unit inspection)

    Case 453264 · FAILED

    A legacy L&I inspection label. The unit inspected housing for property-maintenance, fire-prevention, and related code compliance; the separate status says how that visit ended. The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  114. ViolationFIRE EXTING-NEEDS INSP/TAG (Fire extinguisher needs inspection and a current service tag)

    Case 453264 · Violation 3332367 · Code FC-906.2/2 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  115. PermitMechanical

    Permit 530260 · COMPLETED

    MODIFICATIONS TO AN EXISTING HVAC SYSTEM IN A RESEARCH FACILITY THROUGHOUT NEW OFFICE SPACES. WORK TO INCLUDE NEW REGISTERS & DIFFUSERS, EQUIPMENT, FANS AND ALL SUPPLEMENTAL DUCTWORK AS SHOWN IN APPROVED PLANS.

  116. PermitMechanical

    Permit 530259 · COMPLETED

    MODIFICATIONS TO AN EXISTING HVAC SYSTEM THROUGHOUT A RESEARCH FACILITY WHERE NEW OFFICES WERE CREATED. WORK TO INCLUDE NEW REGISTERS & DIFFUSERS, FANS, EXHAUSTS, APPLIANCES AND ALL SUPPLEMENTAL DUCTWORK AS SHOWN IN APPROVED PLANS.

  117. PermitMechanical

    Permit 530256 · COMPLETED

    MODIFICATIONS TO AN HVAC SYSTEM WITHIN AN EXISTING RESEARCH FACILITY WHICH INCLUDE NEW REGISTERS/DIFFUSERS, VAV BOXES AND ALL SUPPLEMENTAL DUCTWORK.

  118. PermitSuppression

    Permit 531871 · COMPLETED

    RELOCATING (2 SPRINKLERS IN THE 7TH FL SWEENEY SPACE OF THE CLINICAL RESEARCH BLDG AT UPENN.

  119. PermitSuppression

    Permit 531872 · COMPLETED

    RELOCATING (4) SPRINKLERS IN THE 7TH FLOOR. DR PROSSER SPACE OF THE CLINICAL RESEARCH BLDG AT UPENN.

  120. PermitPlumbing

    Permit 530291 · COMPLETED

    REPLACE EXISTING SINKS WITH NEW SINKS AND FAUCET ADD EYEWASH STATIONS 6 UTILIZE EXISTING ROUGH IN AND INSTALL INDIRECT WASTE AND TRAP PRIMER FOR HVAC UNIT CONDENSATE (RESEARCH LAB)

  121. PermitPlumbing

    Permit 530293 · COMPLETED

    REPLACE EXISTING SINK WITH NEW SINK AND EYEWASH UTILIZING EXISTING ROUGH IN (RESEARCH LAB)

  122. PermitElectrical

    Permit 522438 · COMPLETED

    ADD 11 LIGHTS, 3 LIGHT SWITCHES, 45 DUPLEX RECEPTS AND 1 PANEL BOARD AS PER 2008 NEC (WEST DISTRICT)

  123. PermitElectrical

    Permit 522439 · COMPLETED

    ADD 4 LIGHTS, 2 LIGHT SWITCHES AND 6 DUPLEX RECEPTS AS PER 2008 NEC (WEST DISTRICT)

  124. PermitMechanical

    Permit 525898 · COMPLETED

    FOR THE INSTALLATION OF TWELVE (12) REGISTERS/DIFFUSERS AND ASSOCIATED DUCT WORK IN CLINICAL RESEARCH BLDG S-4, 6TH FLOOR PER APPROVED PLANS. SEPARATE PERMIT REQUIRED FOR KITCHEN HOODS, ELECTRICAL, PLUMBING, FIRE SUPPRESSION.

  125. PermitElectrical

    Permit 522322 · COMPLETED

    PROVIDE LIGHTING FIXTURES, SWITCHES, RECPTS & BRANCH CKT WIRING, PROVIDE CONDUIT DROPS W/ WALL BOXES & PULL STRINGS (FOR FUTURE PHONE & DATA WIRING BY OTHER) (RESEARCH CENTER)

  126. PermitSuppression

    Permit 527724 · COMPLETED

    INSTALLING OF 13 HEADS TO RELOCATED.

  127. PermitMechanical

    Permit 516554 · COMPLETED

    PARTIAL DEMOLITION OF EXISTING DUCTWORK, PIPING, FAN COIL UNITS, TERMINAL UNITS, PUMPS AND AIR HANDLING UNIT; INSTALLATION OF NEW DUCTWORK, PIPING, HVAC EQUIPMENT WITH ASSOCIATED GRILLES, REGISTERS AND DIFFUSERS AT THE FIRST FLOOR, SECOND FLOOR AND PENTHOUSE LEVELS PER PLANS. SEPARATE PERMITS REQUIRED FOR ANY ELECTRICAL AND PLUMBING WORK.

  128. PermitMajor alteration

    Permit 523387 · COMPLETED

    LEVEL II ALTERATIONS AS PER PLANS.

  129. PermitMajor alteration

    Permit 523375 · COMPLETED

    FOR INTERIOR DEMOLITION & FOR PRESCRIPTIVE ALTERATIONS AT LAB WITHIN EXIST. HIGH-RISE MIXED USE RESEARCH BUILDING TO INCLUDE ERECTION OF DOORWAY OPENING, INFILL OF EXIST. WALL OPENING, & INSTALLATION OF ACT CEILING; WORK AREA IS FULLY SPRINKLERED. SEPARATE PERMIT REQUIRED FOR MECHANICAL, ELECTRICAL, PLUMBING, & FIRE SUPPRESSION WORK.

  130. PermitMajor alteration

    Permit 523383 · COMPLETED

    FOR LEVEL II ALTERATIONS TO AN EXISTING LABORATORY ON THE SEVENTH FLOOR, ALTERATIONS TO INCLUDE THE REMOVAL OF APPLIANCES AND FOR THE ERECTION OF PARTITION WALLS AND PROVIDE FINISHES. ALL WORK TO BE DONE PER APPROVED PLANS. BUILDING IS FULLY SPRINKLERED. SEPARATE PERMITS REQUIRED FOR MECHANICAL, ELECTRICAL, PLUMBING AND FIRE SUPRESSION WORK.

  131. InvestigationHCEU INSP (Housing Code Enforcement Unit inspection)

    Case 414193 · PASSED

    A legacy L&I inspection label. The unit inspected housing for property-maintenance, fire-prevention, and related code compliance; the separate status says how that visit ended. The cited inspection visit was marked passed.

  132. PermitPlumbing

    Permit 517749 · COMPLETED

    NEW PIPING TO FIXTURE LOCATION BOTH POTABLE & ACID DRAINAGE (MEDICAL BLDG)

  133. PermitPlumbing

    Permit 518559 · COMPLETED

    INSTALLATION OF SANITARY WASTE AND VENT, INSTALL DOMESTIC HOT AND COLD WATER PIPING, INSTALL (2) SINKS

  134. PermitMajor alteration

    Permit 514985 · COMPLETED

    LEVEL II INTERIOR ALTERATIONS TO CREATE NEW RESEARCH LABORATORIES IN AN EXISTING BUILDING. BUILDING IS FULLY SPRINKLERED. ALTERATIONS INCLUDE NEW INTERIOR NON-BEARING WALLS, MILLWORK, FINISHES AND FURNITURE. SEPARATE PERMITS REQUIRED FOR ELECTRICAL, MECHANICAL AND FIRE SUPPRESSION SYSTEMS.

  135. PermitElectrical

    Permit 515127 · COMPLETED

    PROVIDE LGT FIXTURES, SWITCHES, RECPTS & BRANCH CKTS WIRING, PROVIDE CONDUIT DROPS W/WALL BOXES & PULL STRINGS FOR FUTURE PHONE & DATA WIRING BY OTHER AS PER NEC 2008 (OFFICES & LABS)

  136. PermitElectrical

    Permit 510948 · COMPLETED

    DISCONNECT AND RECONNECT 4 FUME HOODS AND REMOVE AND REINSTALL 12 RECEPTACLES PER 2008 NEC & NFPA 72(LABS AND OFFICES)

  137. ViolationHAZMAT-ID SIGNS REQ¿D

    Case 414193 · Violation 3036913 · Code FC-2703.5/1 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  138. InvestigationHCEU INSP (Housing Code Enforcement Unit inspection)

    Case 414193 · FAILED

    A legacy L&I inspection label. The unit inspected housing for property-maintenance, fire-prevention, and related code compliance; the separate status says how that visit ended. The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  139. PermitMajor alteration

    Permit 509463 · COMPLETED

    LEVEL II INTERIOR ALTERATIONS AS PER APPROVED PLANS. **SEPARATE PERMITS REQUIRED FOR ANY MEP & FIRE SUPPRESSION WORK**

  140. PermitMechanical

    Permit 505838 · COMPLETED

    ALTERATIONS TO EXISTING HVAC SYSTEM AS PER APPROVED PLANS

  141. CertificationFacade Report

    Certification BC-2022-008465 · Safe with Repair

    Expires 2018-11-22

  142. PermitElectrical

    Permit 495008 · COMPLETED

    RENOVATION TO EXISTING SPACE 143 LIGHTS,70 RECEPTACLES,15 SWITCHES AND 8 STROBES PER 2008 NEC & NFPA 72 (UNIVERSITY)

  143. PermitPlumbing

    Permit 498175 · COMPLETED

    RELOCATION OF LAB SINKS AND INSTALL NEW MIXING VALVES (UNIVERSITY)

  144. PermitMajor alteration

    Permit 496035 · COMPLETED

    LEVEL II ALTERATIONS AS PER PLANS.

  145. PermitSuppression

    Permit 495905 · COMPLETED

    RELOCATING 10 SPRINKLERS IN THE 2ND FLOOR LABORATORY AND THE BASEMENT LABORATORY.

  146. PermitAlteration

    Permit 474668 · COMPLETED

    ROOFING PROJECT.. COMPLETE REMOVAL OF THE EXISTING ROOF SYSTEM DOWN TO THE EXISTING STEEL DECK. INSTALL 2 LAYERS OF 2" THICK INSULATION. INSTALL A FULLY ADHERED FLEECEBACK ROOF SYSTEM. PROVIDED A 15 YEAR MANUFACTERING WARRANTY

  147. PermitSuppression

    Permit 472826 · COMPLETED

    RELOCATE (4) SPRINKLER IN THE 1ST FLOOR IN THE CLINICAL RESEARCH BUILDING

  148. PermitElectrical

    Permit 469857 · COMPLETED

    INSTALL 9 LIGHT 4 SWITCHES 7 POWER OUTLET HOOP UP EXHAUST FAN AND (1) HANDLER UNIT AND UTILIZE EXISTING ELECTRIC SERVICE AS IS *NO FIRE ALARM OR TELE/COM WILL BE INCLUDED* PER 2008 NEC (RESEARCH LAB)

  149. PermitMajor alteration

    Permit 451811 · COMPLETED

    INTERIOR ALTERATIONS TO EXISTING CLINICAL RESEARCH LABS ON FIRST FLOOR AS PER PLANS.

  150. PermitMechanical

    Permit 452165 · COMPLETED

    FOR THE MODIFICATION TO AN EXISTING HVAC SYSTEM TO INCLUDE THE REMOVAL OF EXHAUST HOODS, SUPPLY REGISTERS AND EXHUAST RETURNS AND FOR THE INSTALLATION OF NEW SUPPLY AND RETURN SYSTEMS.

  151. PermitMechanical

    Permit 397600 · COMPLETED

    MECHANICAL WORK. INCLUDES FLEX DUCT INSTALLATION, ROUTE CONDENSATE DRAIN PIPING FROM A/C AND FAN COIL UNITS, REGISTER/DIFFUSER REPLACEMENT, AND EXISTING TERMINAL UNIT UPGRADES WITH INCIDENTAL WORK.

  152. PermitPlumbing

    Permit 450295 · COMPLETED

    3RD & 6TH FLOORS - PLUMBING ALTERATIONS - REPLACE LAB SINKS AND FAUCETS - ORIGINAL LOCATIONS WITH MINOR PIPING CHANGES

  153. PermitSuppression

    Permit 447190 · COMPLETED

    RELOCATE 41 SPRINKLER FOR REVISED CEILING AND WALL LAYOUT

  154. PermitMajor alteration

    Permit 437178 · COMPLETED

    INTERIOR ALTERATIONS TO EXISTING CLINICAL RESEARCH LABS AT FLOORS 3 AND 6, AS PER PLANS.

  155. License issue eventUNIVERSITY OF PENNA TRUSTEES: High Rise L&I license filing initially issued

    License 565196 · Active

    License event. Registration does not prove present operation or storefront occupancy.

  156. PermitElectrical

    Permit 395252 · COMPLETED

    MINOR DEMO, 20 NEW LIGHT FIX ADDING 20 NEW RECETPS AND 10 POWER OUTLETS FROM EXISTING PANEL AS PER 2008 NEC(LAB FOR UNIVERSITY)(NORTH DIST)

  157. PermitPlumbing

    Permit 397370 · COMPLETED

    INSTALLATION OF 3 NEW SINKS AND REPLACEMENT OF EXISTING P-TRAPS (LABORATORY)

  158. PermitMajor alteration

    Permit 385902 · COMPLETED

    ALTERATIONS AS SHOWN ON PLANS - LABS AND OFFICES

  159. PermitMechanical

    Permit 369613 · COMPLETED

    RELOCATE AND REPLACE DIFFUSERS (12) FOR RESEARCH LAB AS PER PLANS.

  160. PermitElectrical

    Permit 367429 · COMPLETED

    MINOR ALTERATIONS OF LAB AREA AS PER DRAWING AS PER 2008 NEC, COLLEGE

  161. PermitSuppression

    Permit 369467 · COMPLETED

    RELOCATE 12 SPRINKLER HEADS - 4TH FLOOR OFFICE

  162. License issue eventUNIVERSITY OF PENNA TRUSTEES: Dumpster License - Private Property L&I license filing initially issued

    License 546485 · Active

    License event. Registration does not prove present operation or storefront occupancy.

  163. PermitMechanical

    Permit 363606 · COMPLETED

    INSTALL NEW SUPPLY/RETURN AND EXHAUST REGISTERS /DIFFUSERS THAT TIE INTO EXISITNG SYSTEM

  164. PermitPlumbing

    Permit 363628 · COMPLETED

    INSTALL 1 CUP SINK AND 1 LAB SINK, ALL SERVICE TIE INTO EXISTING

  165. PermitMajor alteration

    Permit 360592 · COMPLETED

    INTERIOR ALTERATIONS TO LABS AND OFFICES AS PER DRAWINGS.

  166. PermitElectrical

    Permit 361278 · COMPLETED

    DISCONNECT/RECONNECT EXISTING LIGHTING, INSTALL 15 NEW LIGHT FIXTURES, INSTALLATION OF NEW RECEPTACLES AND WIRE MOLD FROM EXISTING PANEL LOCATIONS, INSTALL NEW LIGHT SWITCHES IN FIVE LOCATIONS, ALL AS PER 2008 NEC (WEST DIST)

  167. PermitMajor alteration

    Permit 356938 · COMPLETED

    INTERIOR DEMO & ALTERATIONS, UPGRADES TO FINISHES, NEW EQUIPMENT INSTALLATION, AS PER PLANS. NO CHANGE IN USE OR OCCUPANCY. ADD'L PERMITS REQUIRED: ELECTRICAL, HVAC, PLUMBING, SPRINKLERS

  168. PermitMechanical

    Permit 323285 · COMPLETED

    FOR THE PARTIAL DEMOLITION OF DUCTWORK AND MECHANICAL EQUIPMENT AND FOR THE INSTALLATION OF NEW DUCTWORK, DIFFUSERS AND MECHANICAL EQUIPMENT IN BASEMENT AND AT PENTHOUSE LEVEL AS PER PLANS.

  169. PermitNew Construction

    Permit 323142 · Expired

    FIRE ALARM: INSTALL (11) HEAT DETECTORS, (26) SMOKE DETECTORSK (2) CONTROL MODULES, (14) STROBES, (16) HORN STROBES AS PER NFPA-72(WEST DIST)

  170. PermitElectrical

    Permit 322178 · COMPLETED

    INSTALL 140 LIGHT FIXTURES,93 RECEPTACLES,27 TELE/DATA BACK BOXES, 8 SWITCHES,7 OCCUPANCY SENSORS,REPLACE 3 MAIN BREAKERS AS PER 2008 NEC

  171. PermitSuppression

    Permit 317565 · COMPLETED

    RELOCATION OF (81) SPRINKLERS IN BASEMENT OF HEALTH FACILITY.

  172. PermitMajor alteration

    Permit 276196 · COMPLETED

    LEVEL 2 ALTERATIONS TO PARTIAL BASEMENT LEVEL AS PER PLANS.

  173. PermitFast form building

    Permit 208503 · COMPLETED

  174. PermitMechanical

    Permit 202293 · COMPLETED

    DEMO EXISTING AND INSTALL NEW DUCT WORK, ACCESSORY MECHANICALS, AS PER SUBMITTED PLANS.

  175. PermitPlumbing

    Permit 202303 · COMPLETED

    1 NEW AUTOCLAVE, 1 FLOOR DRAIN, 1 - 1 1/4 BACKFLOW PREVENTOR AND INSTALL 1 1/4 COLD WATER TO AUTOCLAVE AND 1 AIR CONPRESSOR

  176. PermitMajor alteration

    Permit 197432 · COMPLETED

    INTERIOR ALTERATIONS TO MODIFY AN EXISTING SPACE TO INCLUDE REMOVAL OF A NON REQUIRED STAIWAY, IN-FILL FLOOR SYSTEM AND CREATE INTERIOR SPACE TO SUPPORT THE USE OF AN AUTOCLAVE. ALL WORK SHALL BE PERFORMED BY A LICENSED CONTRACTOR. ALL ACTIVITY SHALL COMPLY WITH THE APPROVED PLANS.

  177. PermitFast form building

    Permit 148407 · COMPLETED

  178. PermitElectrical

    Permit 141358 · COMPLETED

    PROVIDE GENERAL LILGHTING FIXTURES, RECEPTS, SWITCHES NAD BRANCH CIRCUIT WIRRING, POWER WIRING FOR HVAC EQUIPMENT NAD GENERAL SCIENCE LAB EQUIPMENT AS PER 2005 NEC, EXCLUDES FIRE ALARM, SECURITY ALARM, TELEPHONE, DATA, SOUND, PAGING AND LOW VOLT WIRING (NORTH DIST)

  179. PermitMechanical

    Permit 141781 · COMPLETED

    FURNISH AND INSTALL AN HVAC SYSTEM TO SUPPORT THE OPERATION OF A TUNNEL WASHER

  180. PermitPlumbing

    Permit 141804 · COMPLETED

    FURNISH AND INSTALL DOMESTIC COLD AND HOT WATER TO A TUNNELL WASHER. (5 SINKS)

  181. PermitMajor alteration

    Permit 112432 · COMPLETED

    INTERIOR ALTERATIONS AS PER PLAN SEPARATE PERMIT REQUIRED FOR MECHANICAL WORK.

  182. PermitMechanical

    Permit 55255 · COMPLETED

    RENOVATION OF EXISTING HVAC SYSTEM, AS PER PLANS

  183. PermitMajor alteration

    Permit 45543 · COMPLETED

    ALTERATIONS TO LABS AND OFFICES AS PART OF UNIVERSITY COMPLEX

  184. PermitFast form building

    Permit 50380 · COMPLETED

Where this comes from

Methodology & freshness

This report was assembled Jul 29, 2026, 8:12 AM ET. Available City datasets are queried from OpenDataPhilly (phl.carto.com) and the cited City ArcGIS feeds; record queries paginate rather than silently taking a first page. For this property: Permits: queried · Violations: queried · Investigations: queried · Appeals: queried · Licenses: queried · Building certifications: queried. “Unavailable” means the source query failed or was not supplied, not “no record.” Reports re-pull on view after seven days and on an overnight rolling schedule; citywide benchmarks recompute weekly. Source dates still govern: the parcel-level tax-delinquency snapshot is June 2022 and the separate detailed tax ledger ends in 2016, so neither establishes today’s balance. The live balance and date-effective payoff must be verified in Tax Center. AI-written passages are grounded in the assembled record and rejected if they state a number the record does not hold.