Commercial property report

1500 Chestnut St

17,500 sqftCMX5built 1900

Property at a glanceCommercial

Gould Chestnut Street LLC

2026 assessment
$4.5M OPA value, not a listing price
2027 published assessment
$4.5M Future roll, not the current tax bill
Neighborhood area
Center City West Approximate · based on ZIP 19102
From above · selected parcel outlined; choose a neighboring polygon to open it — imagery © Esri, Maxar

Assessment and City record timeline

The line tracks this property’s published City assessment. Markers show deeds, permits, inspections, licenses, violations, certifications, and appeals on their recorded dates. Select one to read the filing.

Assessments are tax-roll values, not sale prices or appraisals. OPA has published a 2027 assessment of $4,530,400. It is not yet the billed-year tax basis.

$0$2.5M$5.0M$4.5M201320162019202220252027
Property assessmentAssessmentL&I violationPermitInspection

Scroll horizontally to move through the years. Each icon sits on its recorded date; records without a day are labeled and centered within their year. Select one to explain the filing.

Highlight
Every dated record29 events · exact dates, newest first
  1. PermitAddition and/or Alteration
  2. InspectionL&I investigation
  3. PermitElectrical
  4. L&I violationPENALTY- NO ELEC PERM INFO
  5. L&I violationPERME- INSTALL SERVICE + WIRE
  6. L&I violationPERME- REQUIRED TO CORR VIOL
  7. L&I violationPROTECT-CONDUCTORS
  8. InspectionEP_ELEC
  9. InspectionCI INSP
  10. L&I violationVIOL C&I MESSAGE
  11. L&I violationELEC PROPERLY INSTALL-NR
  12. L&I violationFIRE-ELECT OPEN JUNCTION BOX
  13. InspectionCI INSP
  14. PermitElectrical
  15. InspectionCI INSP
  16. L&I violationEGRESS-INT CLEAR OBSTRUCTION
  17. L&I violationVIOL C&I MESSAGE
  18. InspectionCI INSP
  19. InspectionCI INSP
  20. InspectionCI INSP
  21. L&I violationFIRE-ELECT CLEARANCE REQ
  22. L&I violationVIOL C&I MESSAGE
  23. InspectionCI INSP
  24. InspectionCI INSP
  25. L&I violationFIRE-PULL STATION SIGNS
  26. L&I violationVIOL C&I MESSAGE
  27. L&I violationEXT RUBBISH/EXCESS STORAGE
  28. L&I violationINT MATERIAL STORAGE EQUIP RM
  29. InspectionCI INSP

Verify the public record

$62,480/year estimated property tax

2026 taxable assessment $4,463,500 × 1.3998%. This is an estimate, not a bill or account balance. The City maintains payments, credits, interest, and the current amount due.

OPA has published a 2027 assessment of $4,530,400. It is not the 2026 billed-year value.

Current City balanceCheck Tax Center

Payments, credits, interest, and the current amount due are maintained by the City.

OPA 888114602
Open Philadelphia Tax Center →Use “View period balance” to inspect each tax year.
Exemption classificationNo exemption shown

2026 taxable assessment equals the full assessed value.

Historical delinquency sources No current conclusion

This parcel did not match the June 2022 delinquency snapshot. That absence does not confirm the account is current today.

For a purchase, refinance, or closing, request the City’s official Property Payoff statement in Tax Center under “More options.”

Where the record looks off

Conflicts in City paperwork. Flags on the data, not the property.

"Built 1900" is usually a placeholder

Philadelphia records use 1900 as a stand-in when the real construction year was never documented. Treat the age as unknown, not as 120+ years.

Property report

Commercial property

Commercial, recorded in the City's commercial category. The public record and owner trail follow.

What it is
Commercial Com Condo 1 Sty Masonry
Owner
Gould Chestnut Street LLC
$ / sq ft
$259 above the $151 median for 7,668 commercial parcels citywide
Corridor
Market West city commercial corridor
Interior area
17,500 sqft
Built
1900
Zoning
CMX5

Recorded owner

Who's behind it

Gould Chestnut Street LLC · corporate / LLC owner

• Tax bills mail to 60 Cutter Mill Rd, Great Neck NY, 11021 — outside Philadelphia

Block context

1500 block of Chestnut St. Compare parcels, ownership, and public-record history.

See the whole block →

Next door: 1500 Chestnut St  ·  1500 Chestnut St

No business or residential license records

No business license or residential registration matched this OPA parcel in the latest City data.

Verify with the City ↗
Open every source row 29 dated rows
  1. PermitAddition and/or Alteration

    Permit EP-2024-011907 · Completed

    • Demo existing chiller circuits (power and control) back to 1st junction box in line (believe power conduit is shared by other circuits). • Tap the bus of 1200amp distribution panel/switchgear (surveyed panel) and install (1) 400amp fusible disconnect fused at 400amp (MOCP of the new chiller) next to distribution panel. • Install 2 ½” EMT and 250MCM circuit (sized to Chiller MCA) from 400amp disconnect to new mag bearing chiller location and finish off run to chiller integral disconnect furnished by manufacturer in greenfield flexible conduit. • Re-use conduit and 40amp wire feeding existing chiller (fed from panel SBPP), box and extend conduit circuit to new 20amp exhaust fan “EF-1”; provide new 30amp non-fused disconnect by fan and replace 40amp breaker feeding chiller with 20amp 3 pole circuit breaker. • Install (1) 120volt 20amp circuit with from 120/208volt emergency panel SBRP at top of landing (above chiller) to chiller 120volt control panel. • Install (1) 120volt 20amp circuit in MC cable below ceiling and conduit stub downs at panel locations from 120/208volt emergency panel SBRP at top of landing (above chiller) to “Sherlock” leak detection panel. • Reconnect controls conduit from existing chiller to new chiller (wire and terminations by Fluidics controls division). Installation shall comply with 2017 NEC.

  2. InvestigationL&I investigation

    Case 615157 · PASSED

    The cited inspection visit was marked passed.

  3. PermitElectrical

    Permit 842905 · COMPLETED

    TEMPORARY INSTALLATION OF 13.2KV/480/277 VOLT PADMOUNT TRANSFORMER AND CABLE. NEW TRANSFORMER & CABLE TO BE INSTALLED IN KIND. NO INCREASE IN LOAD OR CHANGE IN EQUIPMENT AS PREVIOUSLY ON SITE.... PER 2008 NEC (MIXED USE)

  4. ViolationPENALTY- NO ELEC PERM INFO

    Case 615157 · Violation 211943433 · Code A-901.13/2 · COMPLIED

    Resolution: COMPLIED - PERMIT OBTAINED City marked this violation complied with; check the resolution date and live case for what was accepted.

  5. ViolationPERME- INSTALL SERVICE + WIRE

    Case 615157 · Violation 211943435 · Code A-301.1/49 · COMPLIED

    Resolution: COMPLIED - PERMIT OBTAINED City marked this violation complied with; check the resolution date and live case for what was accepted.

  6. ViolationPERME- REQUIRED TO CORR VIOL

    Case 615157 · Violation 211943436 · Code A-501.1/3 · COMPLIED

    Resolution: COMPLIED - PERMIT OBTAINED City marked this violation complied with; check the resolution date and live case for what was accepted.

  7. ViolationPROTECT-CONDUCTORS

    Case 615157 · Violation 211943434 · Code E-1201.1/313 · COMPLIED

    Resolution: COMPLIED - PERMIT OBTAINED City marked this violation complied with; check the resolution date and live case for what was accepted.

  8. InvestigationEP_ELEC

    Case 615157 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  9. InvestigationCI INSP

    Case 475992 · PASSED

    The cited inspection visit was marked passed.

  10. ViolationVIOL C&I MESSAGE

    Case 475992 · Violation 3529952 · Code A-000.0/10 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  11. ViolationELEC PROPERLY INSTALL-NR

    Case 475992 · Violation 3529954 · Code PM-506.2/1 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  12. ViolationFIRE-ELECT OPEN JUNCTION BOX

    Case 475992 · Violation 3529953 · Code FC-605.6/1 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  13. InvestigationCI INSP

    Case 475992 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  14. PermitElectrical

    Permit 577750 · COMPLETED

    DISCONNECT & RECONNECT POWER & LIGHTING FOR GONDOLA RELOCATION AS PER NEC 2008 (COMM)

  15. InvestigationCI INSP

    Case 436408 · PASSED

    The cited inspection visit was marked passed.

  16. ViolationEGRESS-INT CLEAR OBSTRUCTION

    Case 436408 · Violation 3213282 · Code FC-1027.4/1 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  17. ViolationVIOL C&I MESSAGE

    Case 436408 · Violation 3213281 · Code A-000.0/10 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  18. InvestigationCI INSP

    Case 436408 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  19. InvestigationCI INSP

    Case 390274 · PASSED

    The cited inspection visit was marked passed.

  20. InvestigationCI INSP

    Case 390274 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  21. ViolationFIRE-ELECT CLEARANCE REQ

    Case 390274 · Violation 2904404 · Code FC-605.3/1 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  22. ViolationVIOL C&I MESSAGE

    Case 390274 · Violation 2904403 · Code A-000.0/10 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  23. InvestigationCI INSP

    Case 390274 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  24. InvestigationCI INSP

    Case 367931 · PASSED

    The cited inspection visit was marked passed.

  25. ViolationFIRE-PULL STATION SIGNS

    Case 367931 · Violation 2704953 · Code FC-907.4/4 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  26. ViolationVIOL C&I MESSAGE

    Case 367931 · Violation 2704950 · Code A-000.0/10 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  27. ViolationEXT RUBBISH/EXCESS STORAGE

    Case 367931 · Violation 2704951 · Code FC-304.1/2 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  28. ViolationINT MATERIAL STORAGE EQUIP RM

    Case 367931 · Violation 2704952 · Code FC-315.2/4 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  29. InvestigationCI INSP

    Case 367931 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

Unavailable when this report assembled: certifications. Unavailable does not mean no record.

Where this comes from

Methodology & freshness

This report was assembled Jul 24, 2026, 2:39 PM ET. Available City datasets are queried from OpenDataPhilly (phl.carto.com) and the cited City ArcGIS feeds; record queries paginate rather than silently taking a first page. For this property: Permits: queried · Violations: queried · Investigations: queried · Appeals: queried · Licenses: queried · Building certifications: unavailable. “Unavailable” means the source query failed or was not supplied, not “no record.” Reports re-pull on view after seven days and on an overnight rolling schedule; citywide benchmarks recompute weekly. Source dates still govern: the parcel-level tax-delinquency snapshot is June 2022 and the separate detailed tax ledger ends in 2016, so neither establishes today’s balance. The live balance and date-effective payoff must be verified in Tax Center. AI-written passages are grounded in the assembled record and rejected if they state a number the record does not hold.

Official city record ↗  ·  L&I history ↗  ·  See the whole block  ·  Download this record (JSON)