Property report

2600 Christian St

224,820 sqftI2

Property at a glanceCommercial

Exelon Generation Company

2026 assessment
$2.5M OPA value, not a listing price
2027 published assessment
$2.5M Future roll, not the current tax bill
Neighborhood area
Graduate Hospital · Point Breeze Approximate · based on ZIP 19146
From above · selected parcel outlined; choose a neighboring polygon to open it — imagery © Esri, Maxar
Open L&I record

6 violation rows marked OPEN in 2 active cases

The actual City titles, code sections, case posture, and latest recorded inspections are shown here instead of only an aggregate count.

Open City history ↗
Case CF-2025-136667

Notice Of Violation

IN VIOLATION

Opened Dec 24, 2025 · Latest inspection FAILED · Apr 23, 2026

  • Suppression System Testing & MaintenanceF-903.5
  • Fire Pumps Testing & MaintenanceF-913.5
  • Fire Hydrant Inspection, Testing, MaintenanceF-507.5.2
  • Inspection, Testing & MaintenanceF-901.6
  • Periodic TestingF-901.6.4
Case CF-2026-012223

Inspection, Testing & Maintenance

IN VIOLATION

Opened Feb 11, 2026 · Latest inspection FAILED · Apr 23, 2026

  • Inspection, Testing & MaintenanceF-901.6

OPEN is the status in the fetched L&I file, not a new inspection by BlockReport. Read the notice for the cited condition and required correction, then verify the live case with L&I.

Assessment and City record timeline

The line tracks this property’s published City assessment. Markers show deeds, permits, inspections, licenses, violations, certifications, and appeals on their recorded dates. Select one to read the filing.

Assessments are tax-roll values, not sale prices or appraisals. OPA has published a 2027 assessment of $2,500,000. It is not yet the billed-year tax basis.

$0$5.0M$10M$2.5M2001200620112016202120262027
Property assessmentAssessmentL&I violationPermitInspectionLicense

Scroll horizontally to move through the years. Each icon sits on its recorded date; records without a day are labeled and centered within their year. Select one to explain the filing.

Highlight
Every dated record109 events · exact dates, newest first
  1. PermitTemporary Tents and Canopies
  2. PermitTemporary Tents and Canopies
  3. InspectionL&I investigation
  4. InspectionL&I investigation
  5. LicenseVicinity Energy Philadelphia, Inc.: Hazardous Materials L&I license filing initially issued
  6. L&I violationINSPECTION, TESTING & MAINTENANCE
  7. InspectionL&I investigation
  8. InspectionL&I investigation
  9. InspectionL&I investigation
  10. L&I violationSUPPRESSION SYSTEM TESTING & MAINTENANCE
  11. L&I violationFIRE PUMPS TESTING & MAINTENANCE
  12. L&I violationFIRE HYDRANT INSPECTION, TESTING, MAINTENANCE
  13. L&I violationINSPECTION, TESTING & MAINTENANCE
  14. L&I violationDUMPSTER LICENSE
  15. L&I violationHAZARDOUS MATERIALS
  16. L&I violationPERIODIC TESTING
  17. PermitTemporary Tents and Canopies
  18. PermitTemporary Tents and Canopies
  19. InspectionL&I investigation
  20. InspectionL&I investigation
  21. L&I violationPERIODIC TESTING
  22. L&I violationINSPECTION, TESTING & MAINTENANCE
  23. L&I violationINSPECTION, TESTING & MAINTENANCE
  24. L&I violationINSPECTION, TESTING & MAINTENANCE
  25. L&I violationMANUAL FIRE ALARM BOX SIGNS
  26. L&I violationSUBMISSION OF CERTIFICATIONS
  27. PermitTemporary Tents and Canopies
  28. PermitGeneral Earth Disturbance ONLY
  29. PermitAddition and/or Alteration
  30. PermitAddition and/or Alterations
  31. PermitAddition and/or Alteration
  32. PermitAlterations
  33. PermitAddition and/or Alteration
  34. InspectionCI INSP
  35. InspectionHCEU INSP (Housing Code Enforcement Unit inspection)
  36. InspectionCI INSP
  37. L&I violationOBTAIN LIC INDICATED (Obtain the license identified in the notice)
  38. InspectionHCEU INSP (Housing Code Enforcement Unit inspection)
  39. L&I violationSPILL CONTROL
  40. L&I violationHAZMAT LICENSE REQUIRED
  41. L&I violationOBTAIN LIC INDICATED (Obtain the license identified in the notice)
  42. L&I violationINCOMPATIBLE MATERIALS
  43. L&I violationVIOL C&I MESSAGE
  44. L&I violationHANDRAILS AND GUARDS
  45. L&I violationPRIVATE FIRE HYDRANT REQ'D
  46. InspectionCI INSP
  47. InspectionCI INSP
  48. PermitOperations
  49. L&I violationVIOL C&I MESSAGE
  50. L&I violationGENERAL REQ.- CITE CODE SECTIO
  51. L&I violationRELEASE OF HAZARDOUS MATERIALS
  52. L&I violationPRIVATE FIRE HYDRANT REQ'D
  53. L&I violationVIOL C&I MESSAGE
  54. L&I violationCUTTING & WELDING (HOT WORK)
  55. L&I violationHAZARDOUS MATERIALS
  56. L&I violationGENERAL REQ.- CITE CODE SECTIO
  57. L&I violationCONTAINER CONTENTS
  58. L&I violationNFPA 704 SIGNS
  59. L&I violationINCOMPATIBLE MATERIALS
  60. L&I violationSPILL CONTROL
  61. L&I violationHYDRANT CERTIFICATION
  62. L&I violationOBTAIN LIC INDICATED (Obtain the license identified in the notice)
  63. L&I violationHANDRAILS AND GUARDS
  64. InspectionCI INSP
  65. InspectionCI INSP
  66. InspectionCI INSP
  67. L&I violationVIOL C&I MESSAGE
  68. L&I violationUNSAFE EQUIPMENT
  69. InspectionCI INSP
  70. InspectionHCEU INSP (Housing Code Enforcement Unit inspection)
  71. InspectionHCEU INSP (Housing Code Enforcement Unit inspection)
  72. L&I violationANNUAL CERT FIRE SUPP
  73. InspectionHCEU INSP (Housing Code Enforcement Unit inspection)
  74. LicenseEXELON GEN CO: Hazardous Materials L&I license filing marked inactive
  75. LicenseEXELON CORPORATION (EXELON GENERATON COMPANY LLC): Hazardous Materials L&I license filing initially issued
  76. PermitAlteration
  77. InspectionHCEU INSP (Housing Code Enforcement Unit inspection)
  78. L&I violationDRAINAGE-DOWNSPOUT REPR/REPLC
  79. InspectionHCEU INSP (Housing Code Enforcement Unit inspection)
  80. PermitElectrical
  81. PermitSuppression
  82. PermitSuppression
  83. PermitDemolition
  84. PermitZoning
  85. PermitElectrical
  86. PermitElectrical
  87. LicenseTRIGEN PHILADELPHIA ENERGY COR: Hazardous Materials L&I license filing marked inactive
  88. PermitOperations
  89. InspectionCI INSP
  90. InspectionCI INSP
  91. PermitOperations
  92. L&I violationVIOL C&I MESSAGE
  93. L&I violationFIRE-PULL STATION SIGNS
  94. L&I violationANNUAL CERT FIRE ALARM
  95. InspectionCI INSP
  96. PermitOperations
  97. L&I violationANNUAL CERT FIRE ALARM
  98. L&I violationVIOL C&I MESSAGE
  99. L&I violationFIRE-PULL STATION SIGNS
  100. InspectionCI INSP
  101. InspectionCI INSP
  102. InspectionCI INSP
  103. InspectionCI INSP
  104. InspectionCI INSP
  105. InspectionCI INSP
  106. InspectionCI INSP
  107. LicensePHILA THERMAL DEV CORP: Dumpster License - Private Property L&I license filing initially issued
  108. LicenseEXELON GEN CO: Hazardous Materials L&I license filing initially issued
  109. LicenseTRIGEN PHILADELPHIA ENERGY COR: Hazardous Materials L&I license filing initially issued

Verify the public record

$34,995/year estimated property tax

2026 taxable assessment $2,500,000 × 1.3998%. This is an estimate, not a bill or account balance. The City maintains payments, credits, interest, and the current amount due.

OPA has published a 2027 assessment of $2,500,000. It is not the 2026 billed-year value.

Current City balanceCheck Tax Center

Payments, credits, interest, and the current amount due are maintained by the City.

OPA 772599000
Open Philadelphia Tax Center →Use “View period balance” to inspect each tax year.
Exemption classificationNo exemption shown

2026 taxable assessment equals the full assessed value.

Historical delinquency sources Record found

This parcel did not match the June 2022 delinquency snapshot. That absence does not confirm the account is current today.

A separate historical parcel ledger ending in 2016 records $217.23 and a lien entry. It is shown as historical context only.

2001$217.23 total · $0.00 principal · $204.93 interest · $0.00 penalty

For a purchase, refinance, or closing, request the City’s official Property Payoff statement in Tax Center under “More options.”

Property report

Commercial property

Commercial, recorded in the City's commercial category. The public record and owner trail follow.

Historical lien entry · through 2016 8 open violations

What it is
Commercial Pub Util 3 Sty Mas+Other
Owner
Exelon Generation Company
$ / sq ft
$11 below the $151 median for 7,668 commercial parcels citywide
Interior area
224,820 sqft
Lot size
477,042 sqft
Zoning
I2

Recorded owner

Who's behind it

Exelon Generation Company · corporate / LLC owner

• Tax bills mail to 13155 Noel Rd, Dallas TX, 75240 — outside Philadelphia

Block context

2600 block of Christian St. Compare parcels, ownership, and public-record history.

See the whole block →

Next door: 2601 Christian St  ·  2603 Christian St

No business or residential license records

No business license or residential registration matched this OPA parcel in the latest City data.

Verify with the City ↗
Open every source row 109 dated rows
  1. PermitTemporary Tents and Canopies

    Permit OP-2026-000202 · Expired

    ASSEMBLY USE TENT - LAWFUL OCCUPANCY SHALL BE AS POSTED - REMOVAL DATE ELECTRICAL PERMIT REQUIRED, UNLESS POWER IS PROVIDED THROUGH EXISTING EXTERIOR GROUND FAULT PROTECTED RECEPTACLES AND POWER CORDS ARE RATED EXTRA HEAVY DUTY WITH U. L. LABEL STATING SUCH RATING. NO COOKING OR HEATING PERMITTED WITH THIS APPROVAL. Streets Department permit is required for street closure prior to the start work if applicable.

  2. PermitTemporary Tents and Canopies

    Permit OP-2026-000164 · Issued

    ASSEMBLY USE TENT - LAWFUL OCCUPANCY SHALL BE AS POSTED - REMOVAL DATE ELECTRICAL PERMIT REQUIRED, UNLESS POWER IS PROVIDED THROUGH EXISTING EXTERIOR GROUND FAULT PROTECTED RECEPTACLES AND POWER CORDS ARE RATED EXTRA HEAVY DUTY WITH U. L. LABEL STATING SUCH RATING. NO COOKING OR HEATING PERMITTED WITH THIS APPROVAL. Streets Department permit is required for street closure prior to the start work if applicable.

  3. InvestigationL&I investigation

    Case CF-2026-012223 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  4. InvestigationL&I investigation

    Case CF-2025-136667 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  5. License issue eventVicinity Energy Philadelphia, Inc.: Hazardous Materials L&I license filing initially issued

    License 1005479 · Active

    License event. Registration does not prove present operation or storefront occupancy.

  6. ViolationINSPECTION, TESTING & MAINTENANCE

    Case CF-2026-012223 · Violation VI-2026-008014 · Code F-901.6 · OPEN

    The individual violation row was marked open in the assembled City file; verify the live notice and any later inspection.

  7. InvestigationL&I investigation

    Case CF-2026-012223 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  8. InvestigationL&I investigation

    Case CF-2025-136667 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  9. InvestigationL&I investigation

    Case CF-2023-105702 · PASSED

    The cited inspection visit was marked passed.

  10. ViolationSUPPRESSION SYSTEM TESTING & MAINTENANCE

    Case CF-2025-136667 · Violation VI-2025-099728 · Code F-903.5 · OPEN

    The individual violation row was marked open in the assembled City file; verify the live notice and any later inspection.

  11. ViolationFIRE PUMPS TESTING & MAINTENANCE

    Case CF-2025-136667 · Violation VI-2025-099730 · Code F-913.5 · OPEN

    The individual violation row was marked open in the assembled City file; verify the live notice and any later inspection.

  12. ViolationFIRE HYDRANT INSPECTION, TESTING, MAINTENANCE

    Case CF-2025-136667 · Violation VI-2025-099738 · Code F-507.5.2 · OPEN

    The individual violation row was marked open in the assembled City file; verify the live notice and any later inspection.

  13. ViolationINSPECTION, TESTING & MAINTENANCE

    Case CF-2025-136667 · Violation VI-2025-099543 · Code F-901.6 · OPEN

    The individual violation row was marked open in the assembled City file; verify the live notice and any later inspection.

  14. ViolationDUMPSTER LICENSE

    Case CF-2025-136667 · Violation VI-2025-099553 · Code 10-722(2)(A) · COMPLIED

    Resolution: COMPLIED - LICENSE/CERTIFICATE/REPORT OBTAINED City marked this violation complied with; check the resolution date and live case for what was accepted.

  15. ViolationHAZARDOUS MATERIALS

    Case CF-2025-136667 · Violation VI-2025-099548 · Code F-105.6.1.8 · COMPLIED

    Resolution: COMPLIED - LICENSE/CERTIFICATE/REPORT OBTAINED City marked this violation complied with; check the resolution date and live case for what was accepted.

  16. ViolationPERIODIC TESTING

    Case CF-2025-136667 · Violation VI-2025-099547 · Code F-901.6.4 · OPEN

    The individual violation row was marked open in the assembled City file; verify the live notice and any later inspection.

  17. PermitTemporary Tents and Canopies

    Permit OP-2025-000251 · Cancelled

    ASSEMBLY USE TENT - LAWFUL OCCUPANCY SHALL BE AS POSTED - REMOVAL DATE ELECTRICAL PERMIT REQUIRED, UNLESS POWER IS PROVIDED THROUGH EXISTING EXTERIOR GROUND FAULT PROTECTED RECEPTACLES AND POWER CORDS ARE RATED EXTRA HEAVY DUTY WITH U. L. LABEL STATING SUCH RATING. NO COOKING OR HEATING PERMITTED WITH THIS APPROVAL. IF TENT IS NOT READY FOR INSPECTION TO INCLUDE ELECTRICAL COMPONENTS, AN ADDITIONAL FEE WILL BE APPLIED FOR ANY AFTER HOURS INSPECTION WITH POSSIBLE ISSUANCE OF CODE VIOLATION NOTICES. ELECTRICAL PERMIT NUMBER MUST BE PROVIDED 24-HRS PRIOR TO EVENT.

  18. PermitTemporary Tents and Canopies

    Permit OP-2024-000209 · Expired

    C#49201 INSTALLING 20X40 CANOPY TENT

  19. InvestigationL&I investigation

    Case 590604 · PASSED

    The cited inspection visit was marked passed.

  20. InvestigationL&I investigation

    Case CF-2023-105702 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  21. ViolationPERIODIC TESTING

    Case CF-2023-105702 · Violation VI-2023-080101 · Code F-901.6.4 · CLOSED

    Resolution: CLOSED - STOP PROCESSING City marked the record closed; open the case for the closing reason.

  22. ViolationINSPECTION, TESTING & MAINTENANCE

    Case CF-2023-105702 · Violation VI-2023-080094 · Code F-901.6 · CLOSED

    Resolution: CLOSED - STOP PROCESSING City marked the record closed; open the case for the closing reason.

  23. ViolationINSPECTION, TESTING & MAINTENANCE

    Case CF-2023-105702 · Violation VI-2023-080093 · Code F-901.6 · CLOSED

    Resolution: CLOSED - STOP PROCESSING City marked the record closed; open the case for the closing reason.

  24. ViolationINSPECTION, TESTING & MAINTENANCE

    Case CF-2023-105702 · Violation VI-2023-080092 · Code F-901.6 · CLOSED

    Resolution: CLOSED - STOP PROCESSING City marked the record closed; open the case for the closing reason.

  25. ViolationMANUAL FIRE ALARM BOX SIGNS

    Case CF-2023-105702 · Violation VI-2023-080104 · Code F-907.4.2.4 · CLOSED

    Resolution: CLOSED - STOP PROCESSING City marked the record closed; open the case for the closing reason.

  26. ViolationSUBMISSION OF CERTIFICATIONS

    Case CF-2023-105702 · Violation VI-2023-080095 · Code F-901.6.4.2 · CLOSED

    Resolution: CLOSED - STOP PROCESSING City marked the record closed; open the case for the closing reason.

  27. PermitTemporary Tents and Canopies

    Permit OP-2023-000391 · Expired

    C#45301 20X40 CANOPY TENT

  28. PermitGeneral Earth Disturbance ONLY

    Permit SP-2022-000301 · Expired

    FOR THE CONSTRUCTION OF NEW DRIVEWAY ACCESS WITH RETAINING WALLS AND FENCE GATE AS PER APPROVED PLANS. **SITE WORK ONLY**

  29. PermitAddition and/or Alteration

    Permit EP-2022-000764 · Completed

    The scope of work is limited to electrical work only. Installation of new 5KV feeders from existing electrical feed inside vicinity project limits. Installation of new 5kV to 480V transformers and switchboard. Installation of two 480V MCC’s with distribution to new equipment being installed. All work as seen on proposed plans as per 2017 nec

  30. PermitAddition and/or Alterations

    Permit MP-2022-000462 · Expired

    For the installation of appliances associated with existing water treatment facility, Appliances to be replace in kind with associated piping and to be done per manufacturer's specifications. All work to be done per approved plans sealed by design engineer. Separate permits required for electrical work. AMENDMENT TO SHOW TIE IN LOCATION

  31. PermitAddition and/or Alteration

    Permit CP-2021-009243 · Expired

    FOR STRUCTURAL ALTERATIONS AND THE INSTALLATION OF DRY FLOOD PROOFING METHODS AS PER APPROVED PLANS. SEPARATE PERMITS REQUIRED FOR ALL OTHER WORK.

  32. PermitAlterations

    Permit PP-2021-019587 · Completed

    Replace House Trap with new FAI

  33. PermitAddition and/or Alteration

    Permit 1021947 · Expired

    ALTERATIONS TO EXISTING ABOVEGROUND STORAGE TANK TO CONSTRUCT SEGREGATION WALL TO SEPARATE MATERIALS STORAGE AREAS AS PER APPROVED PLANS. PERMIT TO ADDRESS CASE NO. 590604.

  34. InvestigationCI INSP

    Case 590604 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  35. InvestigationHCEU INSP (Housing Code Enforcement Unit inspection)

    Case 654162 · PASSED

    A legacy L&I inspection label. The unit inspected housing for property-maintenance, fire-prevention, and related code compliance; the separate status says how that visit ended. The cited inspection visit was marked passed.

  36. InvestigationCI INSP

    Case 579644 · PASSED

    The cited inspection visit was marked passed.

  37. ViolationOBTAIN LIC INDICATED (Obtain the license identified in the notice)

    Case 654162 · Violation 4806654 · Code LO-1 · COMPLIED

    The shorthand does not identify the license type; open the case notice for that detail. City marked this violation complied with; check the resolution date and live case for what was accepted.

  38. InvestigationHCEU INSP (Housing Code Enforcement Unit inspection)

    Case 654162 · FAILED

    A legacy L&I inspection label. The unit inspected housing for property-maintenance, fire-prevention, and related code compliance; the separate status says how that visit ended. The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  39. ViolationSPILL CONTROL

    Case 590604 · Violation 211939731 · Code FC-13-2704.2 · CLOSED

    Resolution: CLOSED - REISSUED/REWRITTEN City marked the record closed; open the case for the closing reason.

  40. ViolationHAZMAT LICENSE REQUIRED

    Case 590604 · Violation 4928469 · Code FC-13-2701.5 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  41. ViolationOBTAIN LIC INDICATED (Obtain the license identified in the notice)

    Case 590604 · Violation 211939777 · Code LO-1 · CLOSED

    The shorthand does not identify the license type; open the case notice for that detail. Resolution: CLOSED - REISSUED/REWRITTEN City marked the record closed; open the case for the closing reason.

  42. ViolationINCOMPATIBLE MATERIALS

    Case 590604 · Violation 211939776 · Code FC-13-270398 · CLOSED

    Resolution: CLOSED - REISSUED/REWRITTEN City marked the record closed; open the case for the closing reason.

  43. ViolationVIOL C&I MESSAGE

    Case 590604 · Violation 211939735 · Code A-000.0/10 · CLOSED

    Resolution: CLOSED - REISSUED/REWRITTEN City marked the record closed; open the case for the closing reason.

  44. ViolationHANDRAILS AND GUARDS

    Case 590604 · Violation 211939734 · Code PM15-307 · CLOSED

    Resolution: CLOSED - REISSUED/REWRITTEN City marked the record closed; open the case for the closing reason.

  45. ViolationPRIVATE FIRE HYDRANT REQ'D

    Case 590604 · Violation 211939733 · Code FC-13-507.51 · CLOSED

    Resolution: CLOSED - REISSUED/REWRITTEN City marked the record closed; open the case for the closing reason.

  46. InvestigationCI INSP

    Case 579649 · PASSED

    The cited inspection visit was marked passed.

  47. InvestigationCI INSP

    Case 590604 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  48. PermitOperations

    Permit 24892 · COMPLETED

    HOTWORKS: WELDING/CUTTING/SOLDERING/TORCH WORK - PERMIT EXPIRES: 5/24/18

  49. ViolationVIOL C&I MESSAGE

    Case 579644 · Violation 4283682 · Code A-000.0/10 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  50. ViolationGENERAL REQ.- CITE CODE SECTIO

    Case 579644 · Violation 4283683 · Code FC-13-2701 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  51. ViolationRELEASE OF HAZARDOUS MATERIALS

    Case 579644 · Violation 4283684 · Code FC-13-2703.3 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  52. ViolationPRIVATE FIRE HYDRANT REQ'D

    Case 579649 · Violation 4283792 · Code FC-13-507.51 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  53. ViolationVIOL C&I MESSAGE

    Case 579649 · Violation 4283784 · Code A-000.0/10 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  54. ViolationCUTTING & WELDING (HOT WORK)

    Case 579649 · Violation 4283785 · Code FC-13-105.65 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  55. ViolationHAZARDOUS MATERIALS

    Case 579649 · Violation 4283786 · Code FC-13-105.69 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  56. ViolationGENERAL REQ.- CITE CODE SECTIO

    Case 579649 · Violation 4283787 · Code FC-13-2701 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  57. ViolationCONTAINER CONTENTS

    Case 579649 · Violation 4283788 · Code FC-13-270181 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  58. ViolationNFPA 704 SIGNS

    Case 579649 · Violation 4283789 · Code FC-13-2703.5 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  59. ViolationINCOMPATIBLE MATERIALS

    Case 579649 · Violation 4283790 · Code FC-13-270398 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  60. ViolationSPILL CONTROL

    Case 579649 · Violation 4283791 · Code FC-13-2704.2 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  61. ViolationHYDRANT CERTIFICATION

    Case 579649 · Violation 4283793 · Code FC-13-507.53 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  62. ViolationOBTAIN LIC INDICATED (Obtain the license identified in the notice)

    Case 579649 · Violation 4283794 · Code LO-1 · COMPLIED

    The shorthand does not identify the license type; open the case notice for that detail. City marked this violation complied with; check the resolution date and live case for what was accepted.

  63. ViolationHANDRAILS AND GUARDS

    Case 579649 · Violation 4283795 · Code PM15-307 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  64. InvestigationCI INSP

    Case 579644 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  65. InvestigationCI INSP

    Case 579649 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  66. InvestigationCI INSP

    Case 539751 · PASSED

    The cited inspection visit was marked passed.

  67. ViolationVIOL C&I MESSAGE

    Case 539751 · Violation 3979270 · Code A-000.0/10 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  68. ViolationUNSAFE EQUIPMENT

    Case 539751 · Violation 3979271 · Code PM15-108.1.2 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  69. InvestigationCI INSP

    Case 539751 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  70. InvestigationHCEU INSP (Housing Code Enforcement Unit inspection)

    Case 469452 · PASSED

    A legacy L&I inspection label. The unit inspected housing for property-maintenance, fire-prevention, and related code compliance; the separate status says how that visit ended. The cited inspection visit was marked passed.

  71. InvestigationHCEU INSP (Housing Code Enforcement Unit inspection)

    Case 469452 · FAILED

    A legacy L&I inspection label. The unit inspected housing for property-maintenance, fire-prevention, and related code compliance; the separate status says how that visit ended. The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  72. ViolationANNUAL CERT FIRE SUPP

    Case 469452 · Violation 3507441 · Code FC-915.1/4 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  73. InvestigationHCEU INSP (Housing Code Enforcement Unit inspection)

    Case 469452 · FAILED

    A legacy L&I inspection label. The unit inspected housing for property-maintenance, fire-prevention, and related code compliance; the separate status says how that visit ended. The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  74. License terminal eventEXELON GEN CO: Hazardous Materials L&I license filing marked inactive

    License 285611 · Inactive

    License event. Registration does not prove present operation or storefront occupancy.

  75. License issue eventEXELON CORPORATION (EXELON GENERATON COMPANY LLC): Hazardous Materials L&I license filing initially issued

    License 609034 · Active

    License event. Registration does not prove present operation or storefront occupancy.

  76. PermitAlteration

    Permit 489538 · COMPLETED

    ROOF REPLACEMENT (BUILT-UP). COMMERCIAL

  77. InvestigationHCEU INSP (Housing Code Enforcement Unit inspection)

    Case 388556 · PASSED

    A legacy L&I inspection label. The unit inspected housing for property-maintenance, fire-prevention, and related code compliance; the separate status says how that visit ended. The cited inspection visit was marked passed.

  78. ViolationDRAINAGE-DOWNSPOUT REPR/REPLC

    Case 388556 · Violation 2843628 · Code PM-302.4/7 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  79. InvestigationHCEU INSP (Housing Code Enforcement Unit inspection)

    Case 388556 · FAILED

    A legacy L&I inspection label. The unit inspected housing for property-maintenance, fire-prevention, and related code compliance; the separate status says how that visit ended. The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  80. PermitElectrical

    Permit 444953 · COMPLETED

    MODIFY EXISTING FIRE ALARM SYSTEM IN THE WATER TREATMENT ,MAINTENENCE SHOP AND 2ND FL OFFICE AREAS AS PER 2008 NEC AND NFPA72(ELECTRIC AND STREAM GENERATING FACILITIES)

  81. PermitSuppression

    Permit 403235 · COMPLETED

    INSTALLING 4 NEW SINGLE INTERLOCKED PREACTION SYSTEMS WITH 12 SPRINKLER HEADS WITHIN THE BOILER ROOMS ON THE LOWER LEVEL IN ACCORDANCE WITH NFPA 13 AND 15 AS PER PLAN.

  82. PermitSuppression

    Permit 400346 · COMPLETED

    INSTALLATION OF CLEAN AGENT FIRE SUPPRESSION SYSTEM IN ACCORDANCE WITH NFPA 2001 PER ENGINEER'S PLANS. SEPARATE PERMIT REQUIRED FOR ELECTRICAL WORK AND ANY OTHER FIRE SUPPRESSION SYSTEMS.

  83. PermitDemolition

    Permit 393920 · COMPLETED

    DEMOLITION OF ABOVE GROUND STORAGE TANK.

  84. PermitZoning

    Permit 394408 · COMPLETED

    DEMOLITION OF ABOVE GRADE TANK.

  85. PermitElectrical

    Permit 383057 · COMPLETED

    ENERGY PLANT-INSTALL CONDT,WIR & INSTRUM,DIST & CTRLS FOR 2 RAPID START BOILERS, 9 PANL BRDS,4 TRANSFMRS, 2 VFD & 3 MOTOR STARTR, RETROFIT ,EXIST SWITCHGEAR TO ACCEPT FEEDERS,INSTALL LT FIXTS,CONDUITS, WIRING & CTRLS, CABLE TRAY & ASSOC GROUNDG & BONDG FOR TRAYS,CONDTS & EQP AS PER 2008 NEC(S DIST)

  86. PermitElectrical

    Permit 353154 · COMPLETED

    INSTALL TRANSFORMER, MCC & SWITCHGEAR. RELOCATE EXISTING FEEDERS FROM EXISTING SWITCHGEAR TO NEW. CONNECT NEW SWITCHGEAR FROM 13KV PECO SOURCE AS PER 2008 NEC. INSTALLATION TO COMPLY WITH ARTICLE 695.3(A)(2).

  87. License terminal eventTRIGEN PHILADELPHIA ENERGY COR: Hazardous Materials L&I license filing marked inactive

    License 285318 · Inactive

    License event. Registration does not prove present operation or storefront occupancy.

  88. PermitOperations

    Permit 13950 · COMPLETED

    10/28/08 - TENT ERECTED ON SITE FOR EVENT

  89. InvestigationCI INSP

    Case 129169 · PASSED

    The cited inspection visit was marked passed.

  90. InvestigationCI INSP

    Case 104898 · PASSED

    The cited inspection visit was marked passed.

  91. PermitOperations

    Permit 1523 · COMPLETED

    10/2/07 - TENT ERECTED @ TRIGEN SITE

  92. ViolationVIOL C&I MESSAGE

    Case 129169 · Violation 686805 · Code A-000.0/10 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  93. ViolationFIRE-PULL STATION SIGNS

    Case 129169 · Violation 686803 · Code FC-907.4/4 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  94. ViolationANNUAL CERT FIRE ALARM

    Case 129169 · Violation 686804 · Code FC-914.1/3 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  95. InvestigationCI INSP

    Case 129169 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  96. PermitOperations

    Permit 1454 · COMPLETED

    9/12/07 - TENT ERECTED @ SITE

  97. ViolationANNUAL CERT FIRE ALARM

    Case 104898 · Violation 513909 · Code FC-914.1/3 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  98. ViolationVIOL C&I MESSAGE

    Case 104898 · Violation 513910 · Code A-000.0/10 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  99. ViolationFIRE-PULL STATION SIGNS

    Case 104898 · Violation 513908 · Code FC-907.4/4 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  100. InvestigationCI INSP

    Case 85714 · PASSED

    The cited inspection visit was marked passed.

  101. InvestigationCI INSP

    Case 104898 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  102. InvestigationCI INSP

    Case 85714 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  103. InvestigationCI INSP

    Case 84147 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  104. InvestigationCI INSP

    Case 84147 · PASSED

    The cited inspection visit was marked passed.

  105. InvestigationCI INSP

    Case 83086 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  106. InvestigationCI INSP

    Case 83086 · PASSED

    The cited inspection visit was marked passed.

  107. License issue eventPHILA THERMAL DEV CORP: Dumpster License - Private Property L&I license filing initially issued

    License 282596 · Active

    License event. Registration does not prove present operation or storefront occupancy.

  108. License issue eventEXELON GEN CO: Hazardous Materials L&I license filing initially issued

    License 285611 · Inactive

    License event. Registration does not prove present operation or storefront occupancy.

  109. License issue eventTRIGEN PHILADELPHIA ENERGY COR: Hazardous Materials L&I license filing initially issued

    License 285318 · Inactive

    License event. Registration does not prove present operation or storefront occupancy.

Unavailable when this report assembled: certifications. Unavailable does not mean no record.

Where this comes from

Methodology & freshness

This report was assembled Jul 27, 2026, 8:17 AM ET. Available City datasets are queried from OpenDataPhilly (phl.carto.com) and the cited City ArcGIS feeds; record queries paginate rather than silently taking a first page. For this property: Permits: queried · Violations: queried · Investigations: queried · Appeals: queried · Licenses: queried · Building certifications: unavailable. “Unavailable” means the source query failed or was not supplied, not “no record.” Reports re-pull on view after seven days and on an overnight rolling schedule; citywide benchmarks recompute weekly. Source dates still govern: the parcel-level tax-delinquency snapshot is June 2022 and the separate detailed tax ledger ends in 2016, so neither establishes today’s balance. The live balance and date-effective payoff must be verified in Tax Center. AI-written passages are grounded in the assembled record and rejected if they state a number the record does not hold.

Official city record ↗  ·  L&I history ↗  ·  See the whole block  ·  Download this record (JSON)