Industrial property report

956 E Erie Ave

1 story375,060 sqftI2built 2023

Property at a glanceIndustrial

W Csv Erie Owner Ix LLC

2026 assessment
$4.9M OPA value, not a listing price
2027 published assessment
$4.9M Future roll, not the current tax bill
Neighborhood area
Port Richmond · Kensington Approximate · based on ZIP 19134
From above · selected parcel outlined; choose a neighboring polygon to open it — imagery © Esri, Maxar
Open L&I record

8 violation rows marked OPEN in 2 active cases

The actual City titles, code sections, case posture, and latest recorded inspections are shown here instead of only an aggregate count.

Open City history ↗
Case CF-2023-120667

Notice Of Violation

IN VIOLATION

Opened Nov 22, 2023 · Latest inspection FAILED · Mar 24, 2024

  • Fire ExtinguishersF-906.2
  • Periodic TestingF-901.6.4
  • Inspection, Testing And MaintenanceF-907.8.5
  • Unapproved ConditionsF-604.6
  • Fdc Locking CapsF-912.4.1
  • Suppression System Testing & MaintenanceF-903.5
  • Fire Extinguishers RequiredF-906.1
Case CF-2025-111820

Inspection, Testing & Maintenance

IN VIOLATION

Opened Oct 9, 2025 · Latest inspection FAILED · Dec 29, 2025

  • Inspection, Testing & MaintenanceF-901.6

OPEN is the status in the fetched L&I file, not a new inspection by BlockReport. Read the notice for the cited condition and required correction, then verify the live case with L&I.

Assessment and City record timeline

The line tracks this property’s published City assessment. Markers show deeds, permits, inspections, licenses, violations, certifications, and appeals on their recorded dates. Select one to read the filing.

Assessments are tax-roll values, not sale prices or appraisals. OPA has published a 2027 assessment of $4,910,500. It is not yet the billed-year tax basis.

$0$2.5M$5.0M$4.9M2006201020142018202220262027
Property assessmentAssessmentL&I violationPermitInspectionCertification

Scroll horizontally to move through the years. Each icon sits on its recorded date; records without a day are labeled and centered within their year. Select one to explain the filing.

Highlight
Every dated record178 events · exact dates, newest first
  1. PermitAddition and/or Alteration
  2. PermitAlterations
  3. PermitAddition and/or Alteration
  4. PermitAddition and/or Alterations
  5. PermitAddition and/or Alterations
  6. PermitAddition and/or Alteration
  7. PermitSign
  8. CertificationFire Alarm Certification
  9. CertificationSprinkler Certification
  10. PermitSigns (Accessory / Non-Accessory)
  11. PermitAddition and/or Alteration
  12. PermitAddition and/or Alteration
  13. PermitAddition and/or Alterations
  14. PermitAddition and/or Alteration
  15. PermitAddition and/or Alterations
  16. PermitAlterations
  17. PermitAddition and/or Alteration
  18. PermitAddition and/or Alteration
  19. InspectionL&I investigation
  20. InspectionL&I investigation
  21. InspectionL&I investigation
  22. L&I violationINSPECTION, TESTING & MAINTENANCE
  23. CertificationFire Alarm Certification
  24. CertificationSprinkler Certification
  25. PermitAddition and/or Alterations
  26. InspectionL&I investigation
  27. CertificationFire Alarm Certification
  28. InspectionL&I investigation
  29. PermitAddition and/or Alterations
  30. PermitAlterations
  31. InspectionL&I investigation
  32. InspectionL&I investigation
  33. PermitAddition and/or Alteration
  34. L&I violationFIRE EXTINGUISHER HANGERS & BRACKETS
  35. L&I violationFIRE EXTINGUISHERS
  36. L&I violationWORKING SPACE & CLEARANCE
  37. L&I violationFIRE EXTINGUISHER UNOBSTRUCTED & UNOBSCURED
  38. L&I violationPERIODIC TESTING
  39. L&I violationINSPECTION, TESTING AND MAINTENANCE
  40. L&I violationELECTRICAL- HAZARD
  41. L&I violationUNAPPROVED CONDITIONS
  42. L&I violationFDC LOCKING CAPS
  43. L&I violationSUPPRESSION SYSTEM TESTING & MAINTENANCE
  44. L&I violationEMERGENCY LIGHTING POWER TEST
  45. L&I violationFIRE RESISTANCE RATED CONSTRUCTION
  46. L&I violationFIRE EXTINGUISHERS REQUIRED
  47. L&I violationEQUIPMENT ROOM FIRE DEPT ACCESS
  48. L&I violationLIGHTING
  49. L&I violationFDC SIGNAGE REQUIRED
  50. CertificationFire Alarm Certification
  51. PermitAddition and/or Alterations
  52. PermitAddition and/or Alteration
  53. PermitAlterations
  54. PermitAddition and/or Alteration
  55. PermitAddition and/or Alteration
  56. PermitTemporary Tents and Canopies
  57. PermitNew Construction
  58. PermitNew Construction
  59. PermitNew Construction
  60. PermitAlterations
  61. InspectionL&I investigation
  62. L&I violationUNAPPROVED CONDITIONS
  63. L&I violationEXIT DOORS
  64. L&I violationDAMPER CERTIFICATION REPORT
  65. L&I violationEMERGENCY LIGHTING POWER TEST
  66. L&I violationLIGHTING
  67. L&I violationEQUIPMENT ACCESS
  68. L&I violationEQUIPMENT ROOMS
  69. L&I violationFIRE PROTECTION ROOM IDENTIFICATION
  70. L&I violationFIRE EXTINGUISHER UNOBSTRUCTED & UNOBSCURED
  71. L&I violationFIRE EXTINGUISHERS
  72. L&I violationSUPPRESSION SYSTEM TESTING & MAINTENANCE
  73. L&I violationINSPECTION, TESTING & MAINTENANCE
  74. L&I violationINSPECTION, TESTING & MAINTENANCE
  75. L&I violationRE-INSPECTION & TESTING
  76. PermitNew Construction
  77. PermitNew Construction (Shell Only)
  78. CertificationFire Alarm Certification
  79. PermitFoundation
  80. PermitAlterations
  81. PermitAddition and/or Alteration
  82. PermitMajor Demolition
  83. PermitGeneral Earth Disturbance ONLY
  84. PermitInterior Non-Load-Bearing Wall Demo.
  85. PermitNew construction, addition, GFA change
  86. InspectionL&I investigation
  87. PermitAddition and/or Alterations
  88. InspectionL&I investigation
  89. InspectionL&I investigation
  90. InspectionL&I investigation
  91. L&I violationFIRE SYSTEMS MAINTAINED
  92. PermitAddition and/or Alterations
  93. PermitAddition and/or Alteration
  94. PermitAddition and/or Alteration
  95. InspectionL&I investigation
  96. InspectionL&I investigation
  97. PermitAlterations
  98. PermitRough-In
  99. CertificationSprinkler Certification
  100. PermitAddition and/or Alterations
  101. PermitAddition and/or Alterations
  102. InspectionL&I investigation
  103. InspectionL&I investigation
  104. PermitAddition and/or Alteration
  105. PermitAddition and/or Alteration
  106. PermitRough-In
  107. InspectionL&I investigation
  108. L&I violationOUT-OF-SERVICE TAG
  109. L&I violationTEMPERATURE OF PUMP ROOMS
  110. L&I violationFIRE SYSTEMS MAINTAINED
  111. L&I violationNFPA 704 SIGNS
  112. L&I violationFIRE WATCH REQUIRED
  113. InspectionL&I investigation
  114. InspectionL&I investigation
  115. PermitAddition and/or Alteration
  116. PermitChange of Use
  117. InspectionL&I investigation
  118. L&I violationFIRE SYSTEMS MAINTAINED
  119. L&I violationFIRE PUMPS IN VIOLATION OF SECTION F-913
  120. L&I violationFIRE SYSTEMS MAINTAINED
  121. L&I violationFDC SIGNAGE REQUIRED
  122. L&I violationFIRE PUMPS TESTED
  123. L&I violationFIRE SUPPRESSION CERTIFICATION
  124. L&I violationFIRE EXTINGUISHING SYSTEMS
  125. L&I violationFIRE ALARM TESTED/CERTIFIED
  126. PermitElectrical
  127. InspectionPRECOURT (likely: pre-court compliance inspection)
  128. PermitElectrical
  129. PermitElectrical
  130. PermitPlumbing
  131. PermitAdministrative
  132. PermitSuppression
  133. PermitSuppression
  134. PermitMechanical
  135. PermitElectrical
  136. PermitPlumbing
  137. PermitMajor alteration
  138. PermitAlteration
  139. PermitMechanical
  140. PermitUse
  141. PermitMajor alteration
  142. PermitUse
  143. PermitElectrical
  144. InspectionPRECOURT (likely: pre-court compliance inspection)
  145. InspectionPRECOURT (likely: pre-court compliance inspection)
  146. InspectionPRECOURT (likely: pre-court compliance inspection)
  147. InspectionPRECOURT (likely: pre-court compliance inspection)
  148. InspectionCI INSP
  149. InspectionHCEU INSP (Housing Code Enforcement Unit inspection)
  150. PermitDemolition
  151. InspectionHCEU INSP (Housing Code Enforcement Unit inspection)
  152. InspectionHCEU INSP (Housing Code Enforcement Unit inspection)
  153. InspectionCI INSP
  154. L&I violationEXTERIOR AREA SANITATION
  155. L&I violationEXTERIOR AREA WEEDS
  156. InspectionHCEU INSP (Housing Code Enforcement Unit inspection)
  157. InspectionCI INSP
  158. L&I violationDEFECTIVE CONTAINERS/TANKS
  159. InspectionHCEU INSP (Housing Code Enforcement Unit inspection)
  160. L&I violationANNUAL CERT FIRE ALARM
  161. L&I violationFA-REPAIR SYSTEM
  162. InspectionHCEU INSP (Housing Code Enforcement Unit inspection)
  163. InspectionBC INSP (likely: building-code inspection)
  164. InspectionCI INSP
  165. InspectionCI INSP
  166. L&I violationANNUAL CERT FIRE ALARM
  167. InspectionCI INSP
  168. InspectionHCEU INSP (Housing Code Enforcement Unit inspection)
  169. L&I violationEXT A-CLEAN WEEDS/PLANTS (Cut or remove weeds and overgrowth from the exterior area)
  170. InspectionHCEU INSP (Housing Code Enforcement Unit inspection)
  171. PermitUse
  172. PermitPlumbing
  173. PermitElectrical
  174. PermitElectrical
  175. PermitElectrical
  176. PermitPlumbing
  177. InspectionHCEU INSP (Housing Code Enforcement Unit inspection)
  178. InspectionHCEU INSP (Housing Code Enforcement Unit inspection)

Verify the public record

$0/year estimated property tax

2026 taxable assessment $0 × 1.3998%. This is an estimate, not a bill or account balance. The City maintains payments, credits, interest, and the current amount due.

OPA has published a 2027 assessment of $4,910,500. It is not the 2026 billed-year value.

Current City balanceCheck Tax Center

Payments, credits, interest, and the current amount due are maintained by the City.

OPA 884108500
Open Philadelphia Tax Center →Use “View period balance” to inspect each tax year.
Exemption classificationFull assessment exemption shown

2026 OPA shows a zero or de minimis taxable assessment. The open assessment split does not establish the exemption's legal basis, continuing eligibility, or treatment after a transfer.

Historical delinquency sources No current conclusion

This parcel did not match the June 2022 delinquency snapshot. That absence does not confirm the account is current today.

For a purchase, refinance, or closing, request the City’s official Property Payoff statement in Tax Center under “More options.”

Property report

Industrial property

Industrial, recorded in the City's industrial category. The public record and owner trail follow.

17 open violations

What it is
Industrial Ind Light Mfg Masonry+Oth
Owner
W Csv Erie Owner Ix LLC
$ / sq ft
$13 below the $70 median for 3,574 industrial parcels citywide
Interior area
375,060 sqft
Lot size
845,353 sqft
Stories
1
Built
2023
Zoning
I2

Recorded owner

Who's behind it

W Csv Erie Owner Ix LLC · corporate / LLC owner

Nothing beyond the deed name in the assessor's record. Ask a cited question to research the owner's public property record.

Block context

900 block of E Erie Ave. Compare parcels, ownership, and public-record history.

See the whole block →

Next door: 949 E Erie Ave

No business or residential license records

No business license or residential registration matched this OPA parcel in the latest City data.

Verify with the City ↗
Open every source row 177 dated rows
  1. PermitAddition and/or Alteration

    Permit EP-2026-004450 · Completed

    Connect (2) wall signs to existing circuit. No new wiring or building permit involved. General Permit #GP-2026-000745

  2. PermitAlterations

    Permit PP-2026-004226 · Completed

    Rough 4 Bathrooms, Mop Sink, Kitchen sink, water fountain and Hot water heater.

  3. PermitAddition and/or Alteration

    Permit EP-2026-003248 · Completed

    Wiring for new warehouse office and fire alarm. All work per approved plans. No review required for electrical plans the work area is less than 2,000sqft

  4. PermitAddition and/or Alterations

    Permit MP-2026-001534 · Completed

    FOR THE INSTALLATION OF REGISTERS, DIFFUSERS AND APPLIANCES WITH ASSOCIATED DUCTWORK. APPLIANCES TO BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER’S SPECIFICATIONS. ALL WORK TO BE DONE PER APPROVED PLANS. IF FIELD CONDITIONS VARY CONTACT DESIGN ENGINEER PRIOR TO THE START OF ANY WORK.

  5. PermitAddition and/or Alterations

    Permit FP-2026-000494 · Completed

    EZ PERMIT SPRINKLER RELOCATION (NFPA 13)- For the relocation of sprinkler heads as per attached standards. Deviations from these standards require submission of construction and site plans. Relocate 20 sprinkler heads

  6. PermitAddition and/or Alteration

    Permit CP-2026-001389 · Completed

    FOR LEVEL II ALTERATIONS TO AN EXISTING STRUCTURE. ALTERATIONS TO INCLUDE THE ERECTION OF PARTITION WALLS, NEW BATHROOMS, A NEW ENTRANCE RAMP, PROVIDE FINISHES/FURNISHINGS AND ACCESSIBILITY IMPROVMENTS THROUGHOUT. ALL WORK TO BE DONE PER APPROVED PLANS. IF FIELD CONDITIONS VARY CONTACT DESIGN ENGINEER PRIOR TO THE START OF ANY WORK. SEPARATE PERMITS TO BE OBTAINED FOR ALL OTHER WORK.

  7. PermitSign

    Permit GP-2026-000745 · Issued

    FOR THE INSTALLATION OF TWO STATICALLY ILLUMINATED FLAT WALL SIGNS AS PER APPROVED PLANS.

  8. CertificationFire Alarm Certification

    Certification BC-2026-004563 · Certified

    Expires 2027-02-18

  9. CertificationSprinkler Certification

    Certification BC-2026-012974 · Certified

    Expires 2027-02-18

  10. PermitSigns (Accessory / Non-Accessory)

    Permit ZP-2026-001017 · Issued

    FOR THE INSTALLATION OF TWO STATICALLY ILLUMINATED FLAT WALL SIGNS, SIZE AND LOCATION AS SHOWN ON THE PLANS.

  11. PermitAddition and/or Alteration

    Permit EP-2026-000146 · Completed

    Installation of new fire alarm notification devices for tenant fit-out of an existing warehouse space as shown in the attached plans and as per 2016 NFPA 72.

  12. PermitAddition and/or Alteration

    Permit CP-2026-000123 · Completed

    INSTALLATION OF HIGH-PILED STORAGE RACKING SYSTEM WITHIN PREVIOUSLY APPROVED WAREHOUSE FACILITY (SEE PERMIT CP-2025-006134) AS PER APPROVED PLANS. BUILDING TO BE FULLY SPRINKLERED. *2018 IEBC REVIEW*

  13. PermitAddition and/or Alterations

    Permit FP-2025-002421 · Completed

    EZ PERMIT SPRINKLER RELOCATION (NFPA 13)- For the relocation of sprinkler heads as per attached standards. Deviations from these standards require submission of construction and site plans. Relocate 25 sprinkler heads

  14. PermitAddition and/or Alteration

    Permit EP-2026-000134 · Completed

    Install telecommunication wiring for tenant fit out in existing warehouse space. All work to be done according to the 2017 NEC.

  15. PermitAddition and/or Alterations

    Permit MP-2026-000023 · Completed

    Mechanical / Fuel Gas Permit for combo CP-2025-006134

  16. PermitAlterations

    Permit PP-2026-000062 · Completed

    Interior tenant fit-out. Installation of drainage, waste, vent, and water supply for listed fixtures connecting to existing metallic piping. Venting to be designed and installed in accordance with section 919 Philadelphia single stack vent system. All work to be performed in strict compliance with 2018 PPC and approved plans.

  17. PermitAddition and/or Alteration

    Permit CP-2025-006134 · Completed

    LEVEL II ALTERATIONS TO FIT-OUT SHELL WAREHOUSE WITH ACCESSORY OFFICE SPACE AS PER APPROVED PLANS. EXISTING BUILDING SPRINKLERED. *2018 IEBC REVIEW* **SEPARATE PERMITS REQUIRED FOR MEP & FIRE SUPPRESSION WORK**

  18. PermitAddition and/or Alteration

    Permit EP-2026-000038 · Completed

    Tenant fit-out of an existing warehouse. Install wiring, lighting, and receptacle outlets. Install feeder and subpanel for new branch circuits. ALL WORK TO BE DONE ACCORDING TO THE 2017 NEC AND PER APPROVED PLANS.

  19. InvestigationL&I investigation

    Case CF-2025-111820 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  20. InvestigationL&I investigation

    Case CF-2025-111820 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  21. InvestigationL&I investigation

    Case CF-2025-111820 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  22. ViolationINSPECTION, TESTING & MAINTENANCE

    Case CF-2025-111820 · Violation VI-2025-080635 · Code F-901.6 · OPEN

    The individual violation row was marked open in the assembled City file; verify the live notice and any later inspection.

  23. CertificationFire Alarm Certification

    Certification BC-2025-004916 · Certified

    Expires 2026-02-11

  24. CertificationSprinkler Certification

    Certification BC-2025-004265 · Deficient

  25. PermitAddition and/or Alterations

    Permit MP-2024-000016 · Completed

    FOR THE INSTALLATION OF HVAC APPLIANCES, EQUIPMENT, DUCTWORK AND REGISTERS/DIFFUSERS PER APPROVED PLANS AND MANUFACTURER'S SPECIFICATIONS. *2018 IMC REVIEW*

  26. InvestigationL&I investigation

    Case CF-2023-120667 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  27. CertificationFire Alarm Certification

    Certification BC-2024-006338 · Certified

    Expires 2025-02-21

  28. InvestigationL&I investigation

    Case CF-2023-120667 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  29. PermitAddition and/or Alterations

    Permit FP-2024-000047 · Completed

    EZ PERMIT SPRINKLER RELOCATION (NFPA 13)- For the Relocation of Sprinkler Heads as per attached standards. Deviations from these standards require submission of construction and site plans. Relocate 35 Heads

  30. PermitAlterations

    Permit PP-2023-014559 · Completed

    Rough Water and Drainage to 4 Bathrooms, 4 Toilets 4, lavatory sinks, 1 Kitchen Sink, 1 Water Fountain.

  31. InvestigationL&I investigation

    Case CF-2022-050264 · PASSED

    The cited inspection visit was marked passed.

  32. InvestigationL&I investigation

    Case CF-2023-120667 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  33. PermitAddition and/or Alteration

    Permit EP-2023-010312 · Completed

    INSTALL AN 80 AMP/ 3 POLE CIRCUIT BREAKER IN THE EXISTING PANEL. INSTALL A 3/0 AL FEEDER TO A 100 AMP/ 3 POLE SAFETY SWITCH & 45KVA TRANSFORMER. INSTALL A 150 AMP PANEL & FEEDER. INSTALL LIGHTS, SWITCHES, SENSORS, & RECEPTACLES. PROVIDE POWER TO THE HOT WATER HEATER. ALL WORK IN ACCORDANCE WITH THE 2017 NEC.

  34. ViolationFIRE EXTINGUISHER HANGERS & BRACKETS

    Case CF-2023-120667 · Violation VI-2023-094829 · Code F-906.7 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  35. ViolationFIRE EXTINGUISHERS

    Case CF-2023-120667 · Violation VI-2023-094828 · Code F-906.2 · OPEN

    The individual violation row was marked open in the assembled City file; verify the live notice and any later inspection.

  36. ViolationWORKING SPACE & CLEARANCE

    Case CF-2023-120667 · Violation VI-2023-094846 · Code F-604.3 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  37. ViolationFIRE EXTINGUISHER UNOBSTRUCTED & UNOBSCURED

    Case CF-2023-120667 · Violation VI-2023-094752 · Code F-906.6 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  38. ViolationPERIODIC TESTING

    Case CF-2023-120667 · Violation VI-2023-094751 · Code F-901.6.4 · OPEN

    The individual violation row was marked open in the assembled City file; verify the live notice and any later inspection.

  39. ViolationINSPECTION, TESTING AND MAINTENANCE

    Case CF-2023-120667 · Violation VI-2023-094750 · Code F-907.8.5 · OPEN

    The individual violation row was marked open in the assembled City file; verify the live notice and any later inspection.

  40. ViolationELECTRICAL- HAZARD

    Case CF-2023-120667 · Violation VI-2023-094784 · Code PM15-604.3 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  41. ViolationUNAPPROVED CONDITIONS

    Case CF-2023-120667 · Violation VI-2023-094761 · Code F-604.6 · OPEN

    The individual violation row was marked open in the assembled City file; verify the live notice and any later inspection.

  42. ViolationFDC LOCKING CAPS

    Case CF-2023-120667 · Violation VI-2023-094759 · Code F-912.4.1 · OPEN

    The individual violation row was marked open in the assembled City file; verify the live notice and any later inspection.

  43. ViolationSUPPRESSION SYSTEM TESTING & MAINTENANCE

    Case CF-2023-120667 · Violation VI-2023-094785 · Code F-903.5 · OPEN

    The individual violation row was marked open in the assembled City file; verify the live notice and any later inspection.

  44. ViolationEMERGENCY LIGHTING POWER TEST

    Case CF-2023-120667 · Violation VI-2023-094796 · Code F-1031.10.2 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  45. ViolationFIRE RESISTANCE RATED CONSTRUCTION

    Case CF-2023-120667 · Violation VI-2023-094799 · Code F-701.2 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  46. ViolationFIRE EXTINGUISHERS REQUIRED

    Case CF-2023-120667 · Violation VI-2023-094800 · Code F-906.1 · OPEN

    The individual violation row was marked open in the assembled City file; verify the live notice and any later inspection.

  47. ViolationEQUIPMENT ROOM FIRE DEPT ACCESS

    Case CF-2023-120667 · Violation VI-2023-094802 · Code F-914.2.4 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  48. ViolationLIGHTING

    Case CF-2023-120667 · Violation VI-2023-094803 · Code F-901.4.6.4 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  49. ViolationFDC SIGNAGE REQUIRED

    Case CF-2023-120667 · Violation VI-2023-094813 · Code F-912.5 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  50. CertificationFire Alarm Certification

    Certification BC-2023-014870 · Certified

    Expires 2024-07-18

  51. PermitAddition and/or Alterations

    Permit MP-2023-002989 · Completed

    Mechanical / Fuel Gas Permit for combo CP-2023-003407

  52. PermitAddition and/or Alteration

    Permit EP-2023-006259 · Completed

    Electrical Permit for combo CP-2023-003407

  53. PermitAlterations

    Permit PP-2023-009195 · Completed

    Plumbing Permit (Interior) for combo CP-2023-003407

  54. PermitAddition and/or Alteration

    Permit CP-2023-003407 · Completed

    FOR LEVEL II ALTERATIONS TO INCLUDE NEW PARTITIONS, FIXTURES, FURNISHINGS, FINISHES AS PER APPRVOED PLANS. SEPARATE PERMITS REQUIRED FOR MEP AND FIRE SUPPRESSION WORK.

  55. PermitAddition and/or Alteration

    Permit CP-2022-007227 · Completed

    FOR LEVEL II ALTERATION TO FIT-OUT AN OFFICE SPACE WITHIN THE ONE-STORY WAREHOUSE AS PER APPROVED PLANS. BUILDING TO BE FULLY SPRINKLERED. SEPARATE PERMTS REQUIRED FOR MEP & FP WORK.

  56. PermitTemporary Tents and Canopies

    Permit OP-2022-000348 · Expired

    20x30 temporary canopy tent for ground breaking- 40115 Court Street Ventures-As per 2018 Philadelphia Fire Department.

  57. PermitNew Construction

    Permit EP-2022-005787 · Completed

    Lighting- install 133 LED Hi bay fixtures, 38 LED EM Hi bay fixtures, 9 pole lights, 43 LED wall packs. 15kv incoming switch gear, 2500KVA transformer w 4000A MLO 480v switchgear line up. (2) 600A ,(2) 225A, (1) 400A 480v panels. (3) 150A, (1) 225A, (1) 100A 208V panels. (3) 45KVA transformers, (1) 30kva Transformer, (1) 300Kva Transformer, (1) 75Kva Transformer. (23) unit heaters, (23) Exhaust Fans, (6) Gas fired units, (3) water heaters As per 2017 NEC. (1) fire alarm panel, (20) horn strobe, (6) strobe only, (4) smoke detectors as per 2016 NFPA 72.

  58. PermitNew Construction

    Permit FP-2022-001521 · Completed

    FOR THE INSTALLATION OF A 12-INCH FIRE SERVICE LINE, 12-INCH BACKFLOW PREVENTER, FIRE PUMP AND FIRE SUPPRESSION SYSTEM IN ACCORDANCE WITH APPROVED PLANS, HYDRAULIC CALCULATIONS AND NFPA 13.

  59. PermitNew Construction

    Permit MP-2022-002784 · Completed

    FOR THE INSTALLATION OF HVAC EQUIPMENT TO INCLUDE ROOFTOP APPLIANCES WITH ASSOCIATED FUEL GAS PIPING, EXHAUST FANS WITH ASSOCIATED DUCTWORK AND LOUVERS, AND ELECTRIC HEATERS AS PER APPROVED PLANS AND IN ACCORDANCE WITH 2018 IMC. APPLIANCES TO BE INSTALLED PER MANUFACTURER SPECIFICATIONS. SEPARATE PERMITS TO BE OBTAINED FOR ALL OTHER WORK. IF SITE CONDITIONS VARY, CONTACT DESIGN ENGINEER PRIOR TO START OF WORK. SEE CP-2021-007671 FOR ASSOCIATED BUILDING PERMIT.

  60. PermitAlterations

    Permit PP-2022-007999 · Completed

    Sanitary and domestic water lines for future outlets for future fit out of warehouse space to include 8 roof drains. No new plumbing fixtures.

  61. InvestigationL&I investigation

    Case CF-2022-050264 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  62. ViolationUNAPPROVED CONDITIONS

    Case CF-2022-050264 · Violation VI-2022-039996 · Code F-604.6 · CLOSED

    Resolution: CLOSED - REISSUED/REWRITTEN City marked the record closed; open the case for the closing reason.

  63. ViolationEXIT DOORS

    Case CF-2022-050264 · Violation VI-2022-039999 · Code F-1104.28 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  64. ViolationDAMPER CERTIFICATION REPORT

    Case CF-2022-050264 · Violation VI-2022-040001 · Code F-701.6.1.5 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  65. ViolationEMERGENCY LIGHTING POWER TEST

    Case CF-2022-050264 · Violation VI-2022-040006 · Code F-1031.10.2 · CLOSED

    Resolution: CLOSED - WRITTEN IN ERROR City marked the record closed; open the case for the closing reason.

  66. ViolationLIGHTING

    Case CF-2022-050264 · Violation VI-2022-040010 · Code F-901.4.6.4 · CLOSED

    Resolution: CLOSED - REISSUED/REWRITTEN City marked the record closed; open the case for the closing reason.

  67. ViolationEQUIPMENT ACCESS

    Case CF-2022-050264 · Violation VI-2022-039994 · Code F-509.2 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  68. ViolationEQUIPMENT ROOMS

    Case CF-2022-050264 · Violation VI-2022-039992 · Code F-315.3.3 · CLOSED

    Resolution: CLOSED - REISSUED/REWRITTEN City marked the record closed; open the case for the closing reason.

  69. ViolationFIRE PROTECTION ROOM IDENTIFICATION

    Case CF-2022-050264 · Violation VI-2022-039972 · Code F-509.1 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  70. ViolationFIRE EXTINGUISHER UNOBSTRUCTED & UNOBSCURED

    Case CF-2022-050264 · Violation VI-2022-039959 · Code F-906.6 · CLOSED

    Resolution: CLOSED - REISSUED/REWRITTEN City marked the record closed; open the case for the closing reason.

  71. ViolationFIRE EXTINGUISHERS

    Case CF-2022-050264 · Violation VI-2022-039950 · Code F-906.2 · CLOSED

    Resolution: CLOSED - REISSUED/REWRITTEN City marked the record closed; open the case for the closing reason.

  72. ViolationSUPPRESSION SYSTEM TESTING & MAINTENANCE

    Case CF-2022-050264 · Violation VI-2022-039927 · Code F-903.5 · CLOSED

    Resolution: CLOSED - REISSUED/REWRITTEN City marked the record closed; open the case for the closing reason.

  73. ViolationINSPECTION, TESTING & MAINTENANCE

    Case CF-2022-050264 · Violation VI-2022-039922 · Code F-901.6 · CLOSED

    Resolution: CLOSED - REISSUED/REWRITTEN City marked the record closed; open the case for the closing reason.

  74. ViolationINSPECTION, TESTING & MAINTENANCE

    Case CF-2022-050264 · Violation VI-2022-039917 · Code F-901.6 · CLOSED

    Resolution: CLOSED - REISSUED/REWRITTEN City marked the record closed; open the case for the closing reason.

  75. ViolationRE-INSPECTION & TESTING

    Case CF-2022-050264 · Violation VI-2022-039906 · Code F-106.2.2 · CLOSED

    Resolution: CLOSED - REISSUED/REWRITTEN City marked the record closed; open the case for the closing reason.

  76. PermitNew Construction

    Permit EP-2022-005073 · Completed

    Temporary Power for a Construction Trailer. AS PER 2017 NEC.

  77. PermitNew Construction (Shell Only)

    Permit CP-2021-007671 · Completed

    FOR PARTIAL DEMOLITION OF THE EXISTING STRUCTURES AND FOR THE ERECTION OF AN ADDITION TO CREATE A DETACHED STRUCTURE. FOR A SHELL SPACE WITH FIFTY-SIX (56) ACCESSORY BICYCLE SPACES, FORTY FOUR (44) OFF-STREET LOADING SPACES, AND AN ACCESSORY OFF-STREET SURFACE PARKING LOT CONTAINING TWO HUNDRED & TWENTY-NINE (229) STANDARD PARKING SPACES, SEVEN (7) ACCESSIBLE SPACES, AND ONE HUNDRED & FOUR (104) TRAILER PARKING SPACES. BUILDING TO BE FULLY SPRINKLERED. SEPARATE PERMITS REQUIRED FOR C/O, MEP & FP WORK. Asbestos to be removed prior to start of other works. Amendment to remove the restroom on level I from this shell buidling permit.

  78. CertificationFire Alarm Certification

    Certification BC-2022-006968 · Deficient

  79. PermitFoundation

    Permit SP-2022-000155 · Completed

    FOR PARTIAL DEMOLITION OF EXISTING STRUCTURE AND ERECTION OF FOUNDATION ONLY AS PER APPROVED PLANS.

  80. PermitAlterations

    Permit PP-2022-002844 · Completed

    New construction, interior plumbing. All proposed work to be done in accordance with Philadelphia Plumbing Code 2018.

  81. PermitAddition and/or Alteration

    Permit EP-2021-013652 · Expired

    Johnson Controls/Tyco shall install a Vista-128 burglar alarm system to include a head end panel, power supply, cell communicator, wide and long-range motion detectors, 360-degree motion detectors, door status contacts, and keypad. All work in accordance with the 2017 nec.

  82. PermitMajor Demolition

    Permit DP-2021-002120 · Completed

    COMPLETE DEMOLITION OF EXISTING BUILDING BY MECHANICAL EQUIPMENT. ALL PERMITTED DEMOLITION ACTIVITY TO BE IN ACCORDANCE WITH APPROVED SITE SAFETY DEMOLITION PLAN & SUCH PLAN TO BE MAINTAINED ON SITE AT ALL TIMES. FULL SIDEWALK CLOSURE REQUIRED AS REFLECTED ON APPROVED SITE PLAN AND IN ACCORDANCE WITH SECTION 3306 OF THE IBC. SEPARATE STREET CLOSURE PERMIT REQUIRED PRIOR TO START OF WORK. ***demolition cannot start until the water discontinuance permits have been issued***

  83. PermitGeneral Earth Disturbance ONLY

    Permit SP-2021-000917 · Completed

    SITE WORK FOR PROPOSED NEW CONSTRUCTION TO INCLUDE EARTHWORK/DISTURBANCE AND INSTALLATION OF SUBSURFACE DETENTION BASINS ONLY AS PER APPROVED PLANS. SEPARATE PERMITS REQUIRED FOR CATCH BASINS, CONVEYANCE, PIPE AND SEWER CONNECTIONS. SEE PERMIT CP-2021-007671 FOR NEW CONSTRUCTION WORK.

  84. PermitInterior Non-Load-Bearing Wall Demo.

    Permit GM-2021-010110 · Expired

    For minor construction work at the subject property in accordance with all applicable provisions of the Philadelphia Code, all references codes and standards, and the attached EZ Standard, where included. Deviation from this standard shall result in permit revocation. A separate permit from the Philadelphia Department of Streets is required for any sidewalk and street closures. All means of pedestrian protection required at the site in accordance with the Philadelphia Building Code Chapter 33 shall be in place prior to start of work.

  85. PermitNew construction, addition, GFA change

    Permit ZP-2021-005398 · Completed

    FOR PARTIAL DEMOLITION OF THE EXISTING STRUCTURES AND FOR THE ERECTION OF A DETACHED STRUCTURE. SIZE AND LOCATION AS SHOWN ON PLANS.

  86. InvestigationL&I investigation

    Case CF-2021-061039 · PASSED

    The cited inspection visit was marked passed.

  87. PermitAddition and/or Alterations

    Permit MP-2021-002639 · Completed

    FOR THE INSTALLATION OF A HVAC SYSTEM TO INCLUDE NEW APPLIANCES, REGISTERS, DIFFUSERS, AND ASSOCIATED DUCTWORK THROUGHOUT AN INDOOR PAINTBALL ARENA (GROUP A-3 ASSEMBLY & ENTERTAINMENT) AT THE 1ST FLOOR OF THE EXISTING STRUCTURE. ALL WORK TO BE DONE PER APPROVED PLANS AND IN ACCORDANCE WITH 2018 IMC. APPLIANCES TO BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS. SEPARATE PERMITS TO BE OBTAINED FOR ALL OTHER WORK. IF SITE CONDITIONS VARY, CONTACT DESIGN ENGINEER PRIOR TO START OF WORK. SEE CP-2021-000732 FOR ASSOCIATED ALTERATIONS WORK.

  88. InvestigationL&I investigation

    Case CF-2020-005097 · PASSED

    The cited inspection visit was marked passed.

  89. InvestigationL&I investigation

    Case CF-2021-013374 · PASSED

    The cited inspection visit was marked passed.

  90. InvestigationL&I investigation

    Case CF-2021-061039 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  91. ViolationFIRE SYSTEMS MAINTAINED

    Case CF-2021-061039 · Violation VI-2021-043744 · Code FC-13-901.6 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  92. PermitAddition and/or Alterations

    Permit FP-2021-001775 · Completed

    remove (17) existing Post Indicating Valves (PIVs) due to them being obsolete/unneeded

  93. PermitAddition and/or Alteration

    Permit EP-2021-005663 · Completed

    -install FA Smoke Detectors -install Horn Strobes -install FA Control Panel w/ smoke detector(EX) at F.A.C.U location. -install FA Annunciator Panel As per APPROVED DRAWINGS 2018 Phila Fire Code.

  94. PermitAddition and/or Alteration

    Permit EP-2021-004469 · Completed

    INSTALL LIGHTS, LIGHTING CONTROLS, SWITCHES, RECEPTACLES. PROVIDE WIRING FOR THE MECHANICAL & HVAC EQUIPMENT. INSTALL NEW PANELS D-PP1 & F-1-17, RELOCATE MDP,75KVA TRANSFORMER & PANEL RP-1 . INSTALL WIRELESS FIRE ALARM EQUIPMENT AND DEVICES TO INTERFACE WITH THE BUILDING WIRELESS FIRE ALARM SYSTEM. WORK COMPLETED IN ACCORDANCE WITH THE 2017 NEC & THE 2016 NFPA-72.

  95. InvestigationL&I investigation

    Case CF-2020-005097 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  96. InvestigationL&I investigation

    Case CF-2021-013374 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  97. PermitAlterations

    Permit PP-2021-006759 · Completed

    Alterations: Interior plumbing. All proposed work to be done in accordance with Philadelphia Plumbing Code 2018.

  98. PermitRough-In

    Permit PP-2021-007145 · Completed

    ROUGH IN

  99. CertificationSprinkler Certification

    Certification BC-2021-001487 · Certified

    Expires 2022-04-30

  100. PermitAddition and/or Alterations

    Permit FP-2021-001169 · Completed

    EZ PERMIT SPRINKLER RELOCATION (NFPA 13)- For the Relocation of Sprinkler Heads as per attached standards. Deviations from these standards require submission of construction and site plans. Relocate (61) sprinkler heads first floor unit as per NFPA 13 (CP-2021-000732)

  101. PermitAddition and/or Alterations

    Permit FP-2021-001167 · Expired

    EZ PERMIT SPRINKLER RELOCATION (NFPA 13)- For the Relocation of Sprinkler Heads as per attached standards. Deviations from these standards require submission of construction and site plans. Relocate (121) sprinkler heads as per NFPA 13. First Floor Tenant Unit (Paintball Tenant Fit Out) (CP-2020-006721)

  102. InvestigationL&I investigation

    Case CF-2020-005097 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  103. InvestigationL&I investigation

    Case CF-2021-013374 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  104. PermitAddition and/or Alteration

    Permit EP-2021-002390 · Completed

    (6) 100 AMP SUB PANELS FROM 200 A DISCONNECT 15 KVA 120-208/480V TRANSFORMER BRANCH CIRCUIT WIRING TO SPRINKLER SYSTEM AS PER 2017 NEC.

  105. PermitAddition and/or Alteration

    Permit CP-2021-000732 · Completed

    FOR LEVEL II INTERIOR ALTERATIONS AND CHANGE OF OCCUPANCY PER APPROVED PLANS. TENANT SPACE TO BE FULLY SPRINKLERED WITH NFPA 13.

  106. PermitRough-In

    Permit EP-2021-002388 · Expired

    FOR ROUGH IN (6) 100 AMP SUB PANELS FROM 200 A DISCONNECT 15 KVA 120-208/480 V TRANSFORMER BRUNCH CIRCUIT WIRING TO SPRINKLER SYSTEM AS PER 2017 NEC.

  107. InvestigationL&I investigation

    Case CF-2021-013374 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  108. ViolationOUT-OF-SERVICE TAG

    Case CF-2021-013374 · Violation VI-2021-010597 · Code FC-13-901.7.2 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  109. ViolationTEMPERATURE OF PUMP ROOMS

    Case CF-2021-013374 · Violation VI-2021-010598 · Code FC-13-913.3 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  110. ViolationFIRE SYSTEMS MAINTAINED

    Case CF-2021-013374 · Violation VI-2021-010603 · Code FC-13-901.6 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  111. ViolationNFPA 704 SIGNS

    Case CF-2021-013374 · Violation VI-2021-010607 · Code FC-13-2703.5 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  112. ViolationFIRE WATCH REQUIRED

    Case CF-2021-013374 · Violation VI-2021-010596 · Code FC-13-901.7 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  113. InvestigationL&I investigation

    Case CF-2020-005097 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  114. InvestigationL&I investigation

    Case CF-2020-005097 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  115. PermitAddition and/or Alteration

    Permit CP-2020-006721 · Expired

    LEVEL II ALTERATION TO THE GROUND FLOOR AND EGRESS STAIR OF EXISTING STRUCTURE AS PER APPROVED PLAN.

  116. PermitChange of Use

    Permit 1046197 · Issued

    Assembly and Entertainment; Parks and Open Space - Active Recreation

  117. InvestigationL&I investigation

    Case CF-2020-005097 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  118. ViolationFIRE SYSTEMS MAINTAINED

    Case CF-2020-005097 · Violation VI-2020-001117 · Code FC-13-901.6 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  119. ViolationFIRE PUMPS IN VIOLATION OF SECTION F-913

    Case CF-2020-005097 · Violation VI-2020-001118 · Code FC-13-913 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  120. ViolationFIRE SYSTEMS MAINTAINED

    Case CF-2020-005097 · Violation VI-2020-001119 · Code FC-13-901.6 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  121. ViolationFDC SIGNAGE REQUIRED

    Case CF-2020-005097 · Violation VI-2020-001120 · Code FC-13-912.4 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  122. ViolationFIRE PUMPS TESTED

    Case CF-2020-005097 · Violation VI-2020-001121 · Code FC-13-913.5 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  123. ViolationFIRE SUPPRESSION CERTIFICATION

    Case CF-2020-005097 · Violation VI-2020-001122 · Code FC-13-915.1(A) · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  124. ViolationFIRE EXTINGUISHING SYSTEMS

    Case CF-2020-005097 · Violation VI-2020-001123 · Code FC-13-105.7.1 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  125. ViolationFIRE ALARM TESTED/CERTIFIED

    Case CF-2020-005097 · Violation VI-2020-001124 · Code FC-13-915.1 · COMPLIED

    Resolution: COMPLIED - OWNER REPAIR City marked this violation complied with; check the resolution date and live case for what was accepted.

  126. PermitElectrical

    Permit 988331 · COMPLETED

    1 MDP 225 AMP 277/480 V EQUIPMENT, 3 SUBPANELS WITH STEP DOWN TRANSFORERS(WALLS EXISTING) OLD WORK, 50 OUTLETS, 85 LIGHTS AS PER 2008 NEC (EAST DIST)

  127. InvestigationPRECOURT (likely: pre-court compliance inspection)

    Case 572501 · PASSED

    A follow-up before or during enforcement escalation; confirm the case sequence in the City file. The cited inspection visit was marked passed.

  128. PermitElectrical

    Permit 970366 · COMPLETED

    INSTALL ADDITIONAL CEILING MOUNT SMOKE DETECTORS, CEILING MOUNT HORN STROBES AND PULL STATIONS. INSTALL NOTIFICATION DEVICES NAC POWER SUPPLY AS PER NFPA 72 (NORTH DIST)

  129. PermitElectrical

    Permit 970362 · COMPLETED

    INSTALL ADDITIONAL CEILING MOUNT SMOKE DETECTORS, CEILING MOUNT HORN STROBES AND PULL STATIONS. INSTALL NOTIFICATION DEVICES NAC POWER SUPPLY AS PER NFPA 72 (NORTH DIST)

  130. PermitPlumbing

    Permit 966248 · COMPLETED

    ROUGH IN FOR GANG BATHROOMS AND KITCHEN WATER HEATER AND SANITARY AND POTABLE WATER

  131. PermitAdministrative

    Permit 971657 · COMPLETED

    AMEND PERMIT #947887- TO ELIMINATE WORK FROM THE ORIGINAL PERMIT AND RE-CONFIGURATION OF THE OFFICE SPACE AS PER APPROVED PLANS. SEPARATE PERMIT REQUIRED FOR ANY MEP AND FIRE SUPPRESSION WORK.

  132. PermitSuppression

    Permit 977482 · COMPLETED

    EZ PERMIT SPRINKLER RELOCATION (NFPA 13)- FOR THE RELOCATION OF SPRINKLER HEADS AS PER ATTACHED STANDARDS. DEVIATIONS FROM THESE STANDARDS REQUIRE SUBMISSION OF CONSTRUCTION AND SITE PLANS. RELOCATE 12 SPRINKLER HEADS NEW TENANT FITOUT.

  133. PermitSuppression

    Permit 977485 · COMPLETED

    EZ PERMIT SPRINKLER RELOCATION (NFPA 13)- FOR THE RELOCATION OF SPRINKLER HEADS AS PER ATTACHED STANDARDS. DEVIATIONS FROM THESE STANDARDS REQUIRE SUBMISSION OF CONSTRUCTION AND SITE PLANS. RELOCATE 20 SPRINKLER HEADS NEW TENANT FITOUT.

  134. PermitMechanical

    Permit 965888 · COMPLETED

    FOR THE INSTALLATION OF HVAC SCOPE AS INDICATED ON PROVIDED DRAWINGS - SCOPE TO INCLUDE THE INSTALL OF ALL VRF EQUIPMENT, ELECTRIC UNIT HEATERS, REZNOR PACKAGED AH, GAS FIRED UNIT HEATERS, AIR CURTAIN, EXHAUST FANS, ALL REQUIRED DUCTWORK AND GRD'S AS INDICATED ON PROVIDED DRAWINGS. APPLIANCES TO BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS. ALL WORK TO BE DONE PER APPROVED PLANS. IF FIELD CONDITIONS VARY CONTACT DESIGN ENGINEER PRIOR TO THE START OF ANY WORK. SEPARATE PERMITS REQUIRED FOR ALL OTHER WORK.

  135. PermitElectrical

    Permit 962955 · COMPLETED

    TENANT FIT OUT OF FURNITURE STORE. INSTALLATION OF SERVICE, LIGHTING, PANELS, POWER BRANCH CIRCUITS AND LIGHTING FIXTURES TO 1ST FLOOR/SOUTHEAST WING. ALL WIRING AS PER PLANS AS PER NEC 2017. ROUGH WIRE PERMIT (NORTH DIST)

  136. PermitPlumbing

    Permit 958716 · COMPLETED

    ADJUSTING LOCATION OF BATHROOM LAYOUT, NEW FIXTURES GAS PIPING FOR UNIT HEATERS. THE INSTALLTION WILL COMPLY WITH THE 2004 PHILA PLUMBING CODE.

  137. PermitMajor alteration

    Permit 947887 · COMPLETED

    NO CHANGE IN USE AND OCCUPANCY CLASSIFICATION. LEVEL II INTERIOR ALTERATIONS AS PER APPROVED PLANS. CO ON THIS PERMIT FOR DOCUMENTATION. SEPARATE PERMIT REQUIRED FOR MEP AND FIRE SUPPRESSION WORK. *ASBESTOS ABATEMENT REQUIRED PRIOR TO COMMENCEMENT OF WORK*

  138. PermitAlteration

    Permit 960636 · COMPLETED

    EZ PERMIT RE-ROOFING- FOR THE INSTALLATION OF NEW ROOF COVERINGS ON EXITING ROOFS AS PER ATTACHED STANDARD. DEVIATIONS FROM THESE STANDARDS REQUIRE SUBMISSION OF CONSTRUCTION AND SITE PLANS.

  139. PermitMechanical

    Permit 957916 · COMPLETED

    INSTALLATION OF A NEW HVAC SYSTEM FOR A MIXED USE STRUCTURE AS PER APPROVED PLANS.

  140. PermitUse

    Permit 954934 · COMPLETED

    FOR USE AS LIMITED INDUSTRIAL IN AN EXISTING BUILDING WITH OTHER ESTABLISHED USES. SEE ALTERATION PERMIT # 947887

  141. PermitMajor alteration

    Permit 937280 · COMPLETED

    LEVEL II ALTERATIONS WITH PARTIAL CHANGE OF OCCUPANCY TO CREATE A FURNITURE WAREHOUSE WITH ACCESSORY OFFICE SPACE IN UNIT 'G' OF AN EXISTING BUILDING AS PER APPROVED PLANS. EXISTING BUILDING FULLY SPRINKLERED. **SEPARATE PERMITS REQUIRED FOR ANY MEP OR FIRE SUPPRESSION WORK**

  142. PermitUse

    Permit 943465 · COMPLETED

    USE UNIT "G"OF AN EXISTING BUILDING,24,000 SQ.FT OF THE GROUND FLOOR AS A WAREHOUSE FOR FURNITRUE STORAGE(NOT OPEN TO GENERAL PUBLIC FOR RETAIL SALES). ALL OTHER USES TO REMAIN AS PREVIOUSLY APPROVED. NO CHANGE TO HEIGHT OR DIMENSIONS NO SIGNS ON APPLICATION

  143. PermitElectrical

    Permit 906428 · COMPLETED

    INSTALL ALL STROBES AND HORN/STROBES, INSTALL ALL NAC CIRCUITS, INSTALL AL SLC CIRCUITS, INSTALL FIRE ALARM PANEL & INSTALL MANUAL FA PULL STATION AS PER NPFA 72 EAST DISTRICT

  144. InvestigationPRECOURT (likely: pre-court compliance inspection)

    Case 572501 · FAILED

    A follow-up before or during enforcement escalation; confirm the case sequence in the City file. The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  145. InvestigationPRECOURT (likely: pre-court compliance inspection)

    Case 572501 · FAILED

    A follow-up before or during enforcement escalation; confirm the case sequence in the City file. The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  146. InvestigationPRECOURT (likely: pre-court compliance inspection)

    Case 572501 · FAILED

    A follow-up before or during enforcement escalation; confirm the case sequence in the City file. The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  147. InvestigationPRECOURT (likely: pre-court compliance inspection)

    Case 572501 · FAILED

    A follow-up before or during enforcement escalation; confirm the case sequence in the City file. The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  148. InvestigationCI INSP

    Case 581168 · PASSED

    The cited inspection visit was marked passed.

  149. InvestigationHCEU INSP (Housing Code Enforcement Unit inspection)

    Case 583804 · PASSED

    A legacy L&I inspection label. The unit inspected housing for property-maintenance, fire-prevention, and related code compliance; the separate status says how that visit ended. The cited inspection visit was marked passed.

  150. PermitDemolition

    Permit 799772 · COMPLETED

    REMOVAL OF ONE 20,000GAL ABOVE GROUND STORAGE TANK

  151. InvestigationHCEU INSP (Housing Code Enforcement Unit inspection)

    Case 572501 · CLOSED

    A legacy L&I inspection label. The unit inspected housing for property-maintenance, fire-prevention, and related code compliance; the separate status says how that visit ended. City marked the record closed; open the case for the closing reason.

  152. InvestigationHCEU INSP (Housing Code Enforcement Unit inspection)

    Case 583804 · FAILED

    A legacy L&I inspection label. The unit inspected housing for property-maintenance, fire-prevention, and related code compliance; the separate status says how that visit ended. The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  153. InvestigationCI INSP

    Case 581168 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  154. ViolationEXTERIOR AREA SANITATION

    Case 583804 · Violation 4376910 · Code PM15-302.1 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  155. ViolationEXTERIOR AREA WEEDS

    Case 583804 · Violation 4376911 · Code PM15-302.4 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  156. InvestigationHCEU INSP (Housing Code Enforcement Unit inspection)

    Case 583804 · FAILED

    A legacy L&I inspection label. The unit inspected housing for property-maintenance, fire-prevention, and related code compliance; the separate status says how that visit ended. The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  157. InvestigationCI INSP

    Case 581168 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  158. ViolationDEFECTIVE CONTAINERS/TANKS

    Case 581168 · Violation 4339704 · Code FC-13-273262 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  159. InvestigationHCEU INSP (Housing Code Enforcement Unit inspection)

    Case 572501 · FAILED

    A legacy L&I inspection label. The unit inspected housing for property-maintenance, fire-prevention, and related code compliance; the separate status says how that visit ended. The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  160. ViolationANNUAL CERT FIRE ALARM

    Case 572501 · Violation 4828706 · Code FC-915.1/3 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  161. ViolationFA-REPAIR SYSTEM

    Case 572501 · Violation 4828705 · Code FC-901.6/6 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  162. InvestigationHCEU INSP (Housing Code Enforcement Unit inspection)

    Case 572501 · FAILED

    A legacy L&I inspection label. The unit inspected housing for property-maintenance, fire-prevention, and related code compliance; the separate status says how that visit ended. The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  163. InvestigationCI INSP

    Case 557152 · PASSED

    The cited inspection visit was marked passed.

  164. InvestigationCI INSP

    Case 557152 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  165. ViolationANNUAL CERT FIRE ALARM

    Case 557152 · Violation 4153003 · Code FC-915.1/3 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  166. InvestigationCI INSP

    Case 557152 · FAILED

    The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  167. InvestigationHCEU INSP (Housing Code Enforcement Unit inspection)

    Case 437200 · PASSED

    A legacy L&I inspection label. The unit inspected housing for property-maintenance, fire-prevention, and related code compliance; the separate status says how that visit ended. The cited inspection visit was marked passed.

  168. ViolationEXT A-CLEAN WEEDS/PLANTS (Cut or remove weeds and overgrowth from the exterior area)

    Case 437200 · Violation 3218253 · Code PM-302.3/1 · COMPLIED

    City marked this violation complied with; check the resolution date and live case for what was accepted.

  169. InvestigationHCEU INSP (Housing Code Enforcement Unit inspection)

    Case 437200 · FAILED

    A legacy L&I inspection label. The unit inspected housing for property-maintenance, fire-prevention, and related code compliance; the separate status says how that visit ended. The cited inspection visit was marked failed; later rows may show follow-up or resolution.

  170. PermitUse

    Permit 422606 · COMPLETED

    1ST FLOOR USE TO WAREHOUSE AND LIGHT ASSEMBLY

  171. PermitPlumbing

    Permit 410829 · COMPLETED

    INSTALL WATTS 2" RPZ TYPE BACKFLOW PREVENTER IMMEDIATELY DOWNSTEAM FROM METER AND BYPASS (WAREHOUSE)

  172. PermitElectrical

    Permit 390339 · COMPLETED

    DISCONNECT ONE PUMP MOTOR AND HOOK UP NEW PUMP

  173. PermitElectrical

    Permit 386080 · COMPLETED

    INSTALL FIVE - 20 AMP DUPLEX RECEPTACLES IN WP MC CABLE,10 FEET AWAY FROM 200 AMP SUB FEED PANEL. TO BE USED FOR SMALL 1/8 MOTORS AND PORTABLE POWER TOOLS

  174. PermitElectrical

    Permit 343766 · COMPLETED

    REPLACEMENT ONLY OF BURGLAR ALARM PANEL. REPLACE (5) MOTION DETECTORS, BACKUP BATTERIES. REPLACE KEYPAD. IN ACCORDANCE WITH 2008 NEC

  175. PermitPlumbing

    Permit 199827 · COMPLETED

    METER REDUCTION FROM 2" TO 5/8": CHANGING FITTING TO REDUCE FROM 2" TO 5/8"

  176. InvestigationHCEU INSP (Housing Code Enforcement Unit inspection)

    Case 68943 · CLOSED

    A legacy L&I inspection label. The unit inspected housing for property-maintenance, fire-prevention, and related code compliance; the separate status says how that visit ended. City marked the record closed; open the case for the closing reason.

  177. InvestigationHCEU INSP (Housing Code Enforcement Unit inspection)

    Case 68943 · FAILED

    A legacy L&I inspection label. The unit inspected housing for property-maintenance, fire-prevention, and related code compliance; the separate status says how that visit ended. The cited inspection visit was marked failed; later rows may show follow-up or resolution.

Where this comes from

Methodology & freshness

This report was assembled Jul 26, 2026, 12:53 AM ET. Available City datasets are queried from OpenDataPhilly (phl.carto.com) and the cited City ArcGIS feeds; record queries paginate rather than silently taking a first page. For this property: Permits: queried · Violations: queried · Investigations: queried · Appeals: queried · Licenses: queried · Building certifications: queried. “Unavailable” means the source query failed or was not supplied, not “no record.” Reports re-pull on view after seven days and on an overnight rolling schedule; citywide benchmarks recompute weekly. Source dates still govern: the parcel-level tax-delinquency snapshot is June 2022 and the separate detailed tax ledger ends in 2016, so neither establishes today’s balance. The live balance and date-effective payoff must be verified in Tax Center. AI-written passages are grounded in the assembled record and rejected if they state a number the record does not hold.

Official city record ↗  ·  L&I history ↗  ·  See the whole block  ·  Download this record (JSON)